Theben HTS

Presence detector

ECO-IR DUAL-C NT

F

GB

D

E

NL

I

Bedienungsanleitung 

2

Notice d´utilisation 

22

Installation manual 

42

Manual de instrucciones 62
Istruzioni per l'uso 

82

Gebruikershandleiding 102

Summary of Contents for ECO-IR DUAL-C NT

Page 1: ...103014705 04 09 Theben HTS Presence detector ECO IR DUAL C NT F GB D E NL I Bedienungsanleitung 2 Notice d utilisation 22 Installation manual 42 Manual de instrucciones62 Istruzioni per l uso 82 Gebruikershandleiding 102 ...

Page 2: ... IR DUAL C NT Table of contents 1 Safety 43 2 Function and performance characteristics 44 3 Location Installation 45 4 Start up 49 5 Additional wiring examples 52 6 Test mode 54 7 Technical specifications 55 8 Warranty declaration 57 9 Troubleshooting 58 ...

Page 3: ...afety regulations regarding the manipulation of electrical sy stems must be observed The voltage supply must be disconnected pri or to installation CAUTION The device is maintenance free The warranty terminates if the device is opened or entered with any kind of object Designated use The presence detector is solely intended for the purpose contractually spe cified between the manufacturer and the ...

Page 4: ... A mechanical safety lock protects the detector against unauthorised removal Two switching contacts A and B Light switch on the lighting in case of presence and insufficient brightness and off in case of absence or sufficient brightness In addition the lighting can be switched manually by means of push buttons 2 switching contacts Light relay 230V Double real daylight measurement Manual control by...

Page 5: ... proper detection of persons the ECO IR DUAL C NT requires an unobstructed view of the persons Office equipment plants suspended lamps etc may affect the presence detection shading GB H mont Personnes assises Personnes marchant 2 0m 4 5m x 4 5m 6 0m x 6 0m 0 5m 2 5m 6 0m x 6 0m 8 0m x 8 0m 0 5m 3 0m 7 0m x 7 0m 9 0m x 9 0m 0 5m 3 5m 8 0m x 8 0m 10m x 10m 1 0m 4 0m 11m x 11m 1 0m ...

Page 6: ...46 2 3 1 0 m 0 2 3 1 1 2 3 0 8 4 5 4 5 o Detection range mounting height 3 0m seated persons walking persons ...

Page 7: ...ps is not directed at the detector as this would affect the daylight measurement 3 3 Connection The presence detector ECO IR DUAL C NT must be flush mounted into a concealed housing A suitable frame for surface mounting is also availa ble Please pay attention to the orientation of the device when assembling A window zone B inner zone 3 4 Coding Before use the ECO IR DUAL C NT has to be configured ...

Page 8: ... C NT is configured as a Master AB and thus is able to control two lighting groups To get a Master AB the corresponding code key has to be inserted into the power module ECO IR 541C Stuck the corre sponding sticker Master AB onto the power module ...

Page 9: ...ing contacts A B Light Potentiometer Brightness threshold LUX Scale Transfer zones no working area approx 2 Working areas office conference room approx 4 Activities requiring good visibility laboratory drawing etc 5 Deactivation of brightness measurement on Depending on the installation location natural light intensity furniture re flection characteristics of the room and the furniture it may be n...

Page 10: ...n or 15min remain fixed The switch off delay time applies to both switching outputs together DIP switch Fully Semi automatic mode auto Fully automatic mode The lighting is switched on automatically man Semi automatic mode The lighting must be switched on manu ally by push button or switch Push button Switch control Optional push button or switch operation Multiple push buttons on one control input...

Page 11: ...The Light contact reacts instantaneously on brightness in order to check the brightness threshold If the brightness is insufficient the lighting is switched on LED on and if the brightness is sufficient the lighting is switched off LED off During the service phase switching of the lighting occurs fully automati cally no semi automatic mode The service phase terminates earlier by actuating the push...

Page 12: ...nto the power modules Each Master is responsible for measuring the daylight intensity in one half of the room Master A in zone A Master B in zone B Presence detection is done by all detectors together the P contacts are tied together Set the potentiometer and DIP switches on both detectors Note the settings of the po tentiometer LUX is effective only with the appropriate master Max 10 detectors ca...

Page 13: ...Slave onto the power modules Each Master is responsible for measuring the daylight intensity in one half of the room Master A in zone A Master B in zone B Presence detection is done by all detectors together the P contacts are tied together Set the potentiometer and DIP switches on all detectors Note the settings of the potentiometer LUX is effective only with the appropriate master Max 10 detecto...

Page 14: ...B 3 pulses Master A 4 pulses Master B 5 pulses Slave Fast blinking 4x per second the code key is not recongnized 2 Test mode In case of movement LED on both contacts close In case of absence LED off both contacts open after 10sec NOTE no brightness measurement detector always in fully automatic mode The detector remains permanently in the test mode 6 2 Setting the test mode with QuickSet plus Whil...

Page 15: ...ay output A for light with initial current limitation Nominal voltage 230V 10 Max switching capacity Total of the two switching contacts 1400VA 6AX µ Max number of electronic ballasts A relay or contactor must be connected in case of more powerful devices 16x 1x 58W 8x 2x58W 24x 1x36W 12x 2x36W 24x less than 36W Use of T5 FL When using T5 FL lamps with a comparable wattage the same number of elect...

Page 16: ...EC Depth Diameter Mounting plate 35mm 55mm 70 x 70mm Terminals without screws max 1 5mm2 Size of concealed housing for flush mounting 1 NIS PMI Ambient temperature 0 50 C Degree of protection IP 40 Article numbers ECO IR DUAL C NT 202 0 401 Surface frame for ECO IR 360 907 0 512 QuickSet plus service remote control 907 0 532 clic user remote control 907 0 515 ...

Page 17: ...r third parties undertake alterations to the units If the presence detector is connected to a software controlled system the war ranty for this connection is only valid provided the stated interface specification is adhered to We undertake to repair or replace as quickly as possible all supplied components which have become defective or unusable as a result of demonstrably bad material faulty desi...

Page 18: ...witch off delay time has elapsed self learning effect Disturbing heat sources within the detection range heaters incandescent lamp halogen lamp moving objects e g curtains due to open windows Load el starter devices relay has no interference suppression Light keeps switching on and off blinking Incandescent lamps or halogen lamps controlled via ECO IR deactivate Lux measurement swap incandescent l...

Page 19: ...59 Subject to change without prior notice Errors and omissions excepted GB Dimensions ECO IR DUAL C NT ...

Page 20: ...52 355 17 01 www theben hts ch Die Kontaktadressen für weitere Länder finden Sie auf www theben de Veuillez compulser les adresses pour des pays supplémentaires sur www theben de Please find the contact addresses for additional countries on www theben de Las direcciones de contacto de otros países las encontrará en www theben de Gli indirizzi per ulteriori paesi sono disponibili su www theben de D...