Manual DALI button interface TA 4 S DALI-2
9
5
Connection
The TA 4 S DALI-2 button interfaces are connected to the DALI line.
For operation of the TA 4 S DALI-2, an external DALI supply is required. This DALI supply
must be able to ensure a reliable power supply for all connected DALI participants.
A minimum current of 10 mA per TA 4 S DALI-2 device must be provided.
Plug for connection
lead
DALI connection
A connection lead with plug is supplied for connecting buttons C1 to C4, variable resistors or
Theben temperature sensors T1 and T2. The cable length is 25 cm and can be extended up to
max. 30 m if required.
Connection of buttons C1 to C4
Connection of variable resistors or Theben temperature sensors T1 and T2
BK = Black; BN = Brown; RD = Red; OG = Orange, YE = Yellow; GN = Green; BU = Blue
Only connect potential-free buttons.
Do not connect 230 V to the device. Otherwise the device will be destroyed.