Blinds and switch actuator RMG 8, blinds actuator JMG 4
and switch actuator module RME 8 - EIB
theben
As of: Apr-06 (Subject to change without notice)
Page 16 of 36
3.4 The
Parameters
3.4.1 General
The "General" tab is used for setting the basic parameters.
The parameters that can be set are listed in the table below.
Table 1-1: Parameters on the "General" tab
Designation
Values
Description
Used device(s)
only RMG 8
RMG 8 and RME 8
RMG 8 and RMX 4
Select whether only the basic
device (4 drives) or the basic device
+ an extension (a total of 8 or 6
drives) is/are available
Device keys are
always enabled
only enabled if theben-key for JMG
4 / RMG 8 (item no. 907 0 304) is
plugged
Key lock deactivated
If the option "only enabled if key is
plugged" is selected, the device
keyboard is locked and manual
operation is possible only if a key is
inserted in the interface on the front
of the device.
Manual mode
automatically cleared after 30 min
permanent !
Function of the "manual" button on
the device.
The time limit of 30 minutes
prevents a permanent disturbance of
the system if the "manual" button
was pressed e.g. by unauthorized
persons.
If a time limit is not selected, the
manual mode is exited only if the
following events occur:
•
the button is pressed once more
•
the bus voltage is restored
•
the mains voltage is interrupted
•
the device is reprogrammed