![Theben 2269200 Manual Download Page 56](http://html.mh-extra.com/html/theben/2269200/2269200_manual_1101183056.webp)
Manual operation with push buttons
Optical presence detector thePixa P360 KNX
56
6.3
Manual operation with constant lighting control function
If the lighting is operated manually in function light <constant lighting control..>, the following response occurs in
the corresponding zone:
Example with zone 1:
Push button operation
Response of lighting/detector
ON telegram
The lighting is switched on with an ON telegram of the
button. The override is detected via object 11 and
constant lighting control is activated. In the zone, the
lighting is controlled depending on brightness.
Dimming telegram (4 bit)
The lighting is dimmed with a dimming telegram of the
button. The override is detected via object 13 and,
depending on the set parameter (school/office), the
following response occurs:
school:
Constant lighting control is temporarily interrupted by
manual dimming. The brightness setpoint remains
unchanged.
office:
After manual dimming to current brightness level,
constant lighting control remains temporarily active as
new brightness setpoint. After the time delays have
expired, the configured brightness setpoint will be
restored.
Value telegram (1 byte)
The lighting is dimmed with a value telegram of the
button. The override is detected via object 15, and the
lighting remains at the transmitted value for the
duration of presence until the presence time delay has
expired. Afterwards, the original settings are applied
again.
OFF telegram
The lighting is switched off with an OFF telegram of
the button. The override is detected via object 11, and
the lighting remains on for the duration of the
presence. After the room is vacated and the
corresponding time delay has expired, the zone is
again in normal standard operating mode.