background image

A.  Specifications

 

        • Power Supply: 9 to 16 VDC (optional 24 VDC)

 

        • Power Consumption:  < 2W

 

        • Sampling Rate:  4 samples/second

 

        • Accuracy: ±0.2% full scale ±1

 

        • Display Range:  

-

1999 ~ 9999

 

        • Relay Contact Rating:  1A @ 30VDC

 

        • Case Dimensions: 48 x 24 x 75 mm

 

        • Mounting Cutout Dimension: 45 x 22 mm

 

        • LED Display:  0.28” (7 mm)

 

        • Operating Temperature:  0 ~ 50C, <85% RH 

 

B.  Front Panel

 

A.  Specifications

 

        

1

 Alarm & relay J1 indicator

 

        

2

 Up key

 

        

3

 Shift key

 

        

4

 Set Key

 

        

5

 Maximum & Minimum value indicator 

 

        

6

 Display Window  

 

1. AL on indicates alarm is on & J1 relay is pulled in 
(closed)

 

2. MAX(MIN) on when display window shows the 
maximum value or the time of the MAX.  MAX(MIN) 
blinking when display window shows the minimum 
value or the time of MIN.

 

3. “>“ Shift key: In the parameter setting mode, 
press this key to select the digit to be changed.  In 
the normal operation mode, press this key to change 
the display in the sequence shown in the diagram 
below.

 

4. “˄” Up key: In the parameter setting mode, press 
this key to increase the displayed value.  When dis-
playing Max/Min, press & hold it for 3 seconds to 
clear the Max/Min stored.  In normal function, this 
key has two functions, Show Operation Time & 
Change Display Brightness.  Press & hold this key 
down to show the Operation Time since on.  Re-
lease the key to display the current temperature 
(process value).   Each time the key is pressed, the 
display brightness will also be changed from bright 
to dim or from dim to bright.

 

C.  Parameter Setting

 

      1. Basic Parameter

 

          See [Fig3] for programming flow chart

 

(Press “SET” key then input code 0089 to enter)

 

  Note 1: for correcting the offset at Zero: Display = measu PSb

 

  Note 2: for correcting the error at Max: Display = measu PSbf

 

  Note 3: Digital filter: 0=no filter, 1=weak, 2=medium, 3=strong

 

  Note 4: These parameters define the scale boundary & resolution of the 
display value.  They do not apply to temperature sensors.

 

[Table1] Input Type Options

 

  (TC = Thermocouple Sensor)

 

      2. Alarm Parameter

 

(Press “SET” key then input code 0001 to enter)

 

PMD1XT

-

XX

-

012

-

0 Digital Panel Meter

 

Instruction Manual

 

07

-

2014

 

Page 1 of 2

 

TheSensorConnection.com

 