background image

©Copyright Task Force Tips LLC 2004-2020

4

LIX-300 October 23, 2020 Rev22

1.0 MEANING OF SAFETY SIGNAL WORDS

A safety related message is identified by a safety alert symbol and a signal word to indicate the level of risk involved with a particular

hazard. Per ANSI Z535.6, the definitions of the four signal words are as follows:

2.0 SAFETY

3.0 GENERAL INFORMATION

The Task Force Tips HURRICANE Monitor is a simple, yet effective, fixed location master stream device available in manual and RC

versions.

3.1  MECHANICAL SPECIFICATIONS

.0

Table 3.1

DANGER

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious 

injury.

CAUTION

CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor

or moderate injury.

NOTICE

NOTICE is used to address practices not related to physical injury.

DANGER

An inadequate supply of pressure and/or flow will cause an ineffective stream and can result

in injury or death. Choose operating conditions to deliver adequate fire suppression. See flow

graphs. 

WARNING

Injury or damage can occur from an inadequately supported monitor. The mounting must be 

capable of supporting the nozzle reaction force which can be as high as 1500 lbs. 

WARNING

The stream exiting a nozzle is very powerful and capable of causing injury and property damage.

Make sure the nozzle is securely attached and pointing in a safe direction before water is turned on.

Do not direct water stream to cause injury or damage to persons or property. 

WARNING

Equipment may be damaged if frozen while containing significant amounts of water. Such damage 

may be difficult to detect visually. Subsequent pressurization can lead to injury or death. Any time 

the equipment is subject to possible damage due to freezing, it must be tested and approved for 

use by qualified personnel before being considered safe for use. 

WARNING

On many vehicle installations, the monitor is the highest point on the apparatus. Damage or injury

could occur if there is not sufficient clearance to safely pass under doors or overhead obstructions.

Always check parked position of the monitor before moving. 

CAUTION

The electric drives are current limited but may still produce enough force to cause injury. To avoid

injury from a moving monitor:

• Be aware that the monitor may be remotely operated

• Keep hands and fingers away from pinch points on the monitor

• Never operate the manual override while electric controls are in operation 

MANUAL

ELECTRIC

US

METRIC

US

METRIC

Weight

23 lbs

10.4 kg

39 lbs

17.7 kg

Minimum Flow Area

7.07 in

2

45.6 cm

2

12.6 in

2

81.1 cm

2

Maximum Flow

1250 gpm

5000 L/min

1250 gpm

5000 L/min

Maximum Operating Pressure

200 psi

14 bar

200 psi

14 bar

Operating Temperature Range of 

Fluid

33°F to 120°F (1°C to 50°C)

Storage Temperature Range

-40 to 150°F / -40 to 65°C

Materials

ANSI A356.0-T6 Aluminum, Stainless, Nylon

Summary of Contents for HURRICANE DUAL HANDWHEEL Series

Page 1: ...tft com serial number This equipment is intended for use by trained and qualified emergency services personnel for firefighting All personnel using this equipment shall have completed a course of educ...

Page 2: ...3D VUM with 22 5 CODE RPM outlet and Parralel Shaft Gearbox AKP121111D VUM with 4 5 Quick Connect and 2 5 Gated Elbow AKM1Q1113D VUM RC with 2 5 Quick Connect AKE1T1111D Copyright Task Force Tips LLC...

Page 3: ...TRAVEL STOPS 4 6 ELEVATION TRAVEL STOPS 4 7 NOZZLE INSTALLATION 4 7 1 ER NOZZLE INSTALLATION ORIENTATION 4 8 PRESSURE GAUGE PORT 4 9 AUTOMATIC DRAIN 4 10 TILLER HANDLE INSTALLATION 5 0 OPERATING INSTR...

Page 4: ...ul and capable of causing injury and property damage Make sure the nozzle is securely attached and pointing in a safe direction before water is turned on Do not direct water stream to cause injury or...

Page 5: ...junction with the standard isolation gasket kit Order Part Z FIS4A150S Nominal Operating Voltage 12 or 24 VDC auto sense Minimum Voltage 12 VOLT System 10 VDC at the monitor 24 VOLT System 18 VDC at t...

Page 6: ...Rotation Handle Elevation Handwheel Serial Rotation Lock Lever Flange Pressure Gauge Port Grease Zerk Grease Zerk Automatic Drain Built In Stream Straightener HURRICANE TILLER XFIH T series Elevation...

Page 7: ...Pressure Gauge Port HURRICANE DUAL HANDWHEEL XFIH D series Pressure Gauge Port Control Station Box w Control Buttons Horizontal Motor Grease Zerk Grease Zerk Horizontal Rotation Travel Stop 5 places...

Page 8: ...IH E4 A metric DN80 PN16 200mm 22mm 160mm 8 M16 100 110 N M XFIH E5 A metric DN100 PN16 220mm 22mm 180mm 8 M16 100 110 N M XFIH 6 A 3 NPT Female 4 40 111 8mm N A N A N A N A N A XFIH 7 A 4 NPT Female...

Page 9: ...WN UP 7 5 190 5 1 2 3 0 4 8 S w i n g Full 360 Range of Motion Full 180 Range of Motion 10 8 174 8 1 9 48 3 5 9 149 8 SIDE VIEW 9 7 246 4 FRONT VIEW TOP VIEW HURRICANE MONITOR with Tiller and 4 ANSI F...

Page 10: ...268 6 www t f t com XL 10 5 SERIAL TFT X123456 Read manual before use WARNING DOWN UP Full 360 Range of Motion 1 2 3 0 4 8 S w i n g TOP VIEW 9 7 246 4 Full 180 Range of Motion 5 9 149 8 11 01 279 7 1...

Page 11: ...SIONS CONTINUED Figure 3 7E HURRICANE RC MONITOR Shown without Inlet Fitting see table 3 7 1 for additional height per fitting 90 UP 45 DOWN Range of Motion 5 7 146 3 4 87 15 2 385 5 7 146 16 9 430 11...

Page 12: ...ONTINUED Figure 3 7F HURRICANE MONITOR DUAL HANDWHEEL Shown without Inlet Fitting see table 3 7 1 for additional height per fitting TOP VIEW 360 Continuous Range of Motion 11 3 287 Swing Radius 6 0 15...

Page 13: ...ONAL HEIGHT XFIH 1 A 3 ANSI 125 150 metric DN80 PN20 75 20mm XFIH 2 A 4 ANSI 150 metric DN100 PN20 94 23mm XFIH 4 A metric DN80 PN16 2 80 71mm XFIH 5 A metric DN100 PN16 2 80 71mm XFIH 6 A 3 NPT Femal...

Page 14: ...NTING THE MONITOR The Hurricane Monitor is mounted on a riser pipe by a bolted flange or threaded joint The area around the monitor must be free from obstructions which would limit its range of motion...

Page 15: ...n o ring seal Install the monitor using the following procedure VSA 125 VSA 125 Y4437 VW360x200 04 Y4435 VT10 32SH1 2 Apply VSA 125 blue Loctite to threads on both Cylinder Nuts MONITOR BASE CLAMP WAS...

Page 16: ...RATION PURPOSES ALIGNED STRAIGHT AHEAD REFERENCE MARK Monitor may be unscrewed up to one full rotation from bottomed out condition Monitor will leak if unthreaded more than one rotation 360 from botto...

Page 17: ...nylon tubing gives the wire additional stiffness so it better follows as the Extend A Gun RC extends or retracts Figure 4 4 The Extend A Gun manual override knob may be mounted in any of four possibl...

Page 18: ...Horizontal left right travel stop bolts may be installed in the monitor to limit travel Note that left and right are relative to the Straight Back Reference Mark and refer to the operator s position...

Page 19: ...The figures include installation notes Figure 4 6A Figure 4 6B VERT ICAL R A N G E O F M O T I O N AB O V E 4 5 D E G B E L O W 9 0 D E G Hurricane RC Elevation Travel Hurricane Elevation Travel Full...

Page 20: ...ed if not desired for your application To disable the drain valve 1 Unscrew the drain assembly and remove the screw and washer 2 Flip over the rubber drain valve so the raised edge is against the face...

Page 21: ...take some of the backlash out of the gear drive This will minimize bouncing of the nozzle when the apparatus is traveling Always be sure the monitor is properly parked before moving the truck and know...

Page 22: ...0 750 250 920 380 1000 500 1190 630 NOZZLE INLET PRESSURE NOZZLE DIAMETER 2 8 BAR 4 1 BAR 5 5 BAR 7 BAR FLOW L min REACTION KG FLOW L min REACTION KG FLOW L min REACTION KG FLOW L min REACTION KG 35 m...

Page 23: ...PSI 60 PSI 100 PSI 80 PSI HORIZONTAL DISTANCE FEET VERTICAL DISTANCE FEET VERTICAL DISTANCE M 0 0 4 0 0 80 0 0 0 6 0 0 2 HORIZONTAL DISTANCE M 1 75 INCH TIP 0 10 20 0 20 40 60 80 0 0 40 0 80 0 120 0...

Page 24: ...ing their orifice to match the available flow Consult the nozzle manufacturer for maximum flow and pressure range In all cases do not exceed the maximum rating of the Hurricane Operating Envelope 0 40...

Page 25: ...p nozzle Figure 6 4 1 6 4 2 STREAM STRAIGHTENERS WITH FOG NOZZLES Figure 6 4 2 NOTICE The flow path of a fog nozzle serves as a stream straightener Use of a stream straightener with a fog nozzle will...

Page 26: ...imited warranty if the equipment is or has been misused or neglected including failure to provide reasonable maintenance or if there have been accidents to the equipment or if it has been repaired or...

Page 27: ...ease may be applied to the horizontal worm gear grease port Use medium viscosity automotive chassis grease Apply only enough grease to restore normal operation If greasing does not restore normal oper...

Page 28: ...clear of obstructions 7 There is no damage to any thread or other connection 8 All locks and hold down devices work properly 9 The pressure setting on the relief valve if so equipped is set correctly...

Reviews: