Premier Elite Series Installation Manual
Zone Setup
INS176-15
57
Zone Types
Each zone must be programmed before it is recognised by the
system.
Zone numbers are entered as a three digit number i.e. Zone 1 would
be entered as 001. Each zone consists of a zone type, attributes,
areas and zone text.
When programming zones, first select a zone type then select any
required attributes, assign the zone to an area and then program any
required zone text.
Zone Type + Zone Attributes + Zone Areas + Zone Text = Zone
Programmed.
The following zone types are available:
0 - Not used
A zone that is not monitored by the system, unused zones should be
programmed as ‘Not Used’ or linked out.
1 - Entry/Exit 1
Normally used for the main entry/exit door i.e. Front Door. The zone can
be activat
ed during the exit mode without causing a ‘Fault’. Once the
system/area is armed, activation of the zone will start the ‘Entry 1 Delay’
timer for the selected area.
2 - Entry/Exit 2
Normally used for another entry/exit door that requires a different
entry delay i.e. Back Door, Garage Door etc. The zone can be
activat
ed during the exit mode without causing a ‘Fault’. Once the
system/area is armed, activation of th
e zone will start the ‘Entry 2
Delay’ timer for the selected
area.
If any Entry/Exit zone remains active at the end of the entry time, it will
automatically be omitted until the system has been unset and re-set.
If an Entry/Exit zone type is locked out, ‘Guard Access’ zones in the
same area as the omitted Entry/Exit zone will automatically become
‘Entry/Exit 1’ zones to allow access into the premises without causing
an alarm.
If
an ‘Entry/Exit 1 or 2’ zone type is assigned the ‘Entry/Exit 2’ attribute (see
page 58
), when a zone with the ‘Guard’ attribute activates and causes an
alarm (when the area is fully armed), the zone will become a ‘Guard’ zone for
the duration
of the ‘Abort’ timer.
3 - Guard
Normally used for detection devices such as PIR’s, Door Contacts etc.
This zone type will cause an Intruder alarm if it is activated when the
system/area is armed. This zone type will also activate any output
programmed as ‘Guard Alarm’.
4 - Guard Access
Normally used for detection devices along the entry/exit route. This
zone type will allow the user to walk past the detector without causing a
‘Fault’ during the exit mode or an Intruder alarm during the entry mode,
however, the zone will cause an immediate Intruder alarm if activated at
any other time. This zone type will also start the entry mode when the
system/area is part armed and activate any output programmed as
‘Guard Access Alarm’.
5 - 24Hr Audible
This zone type will cause an internal alarm if it is activated when the
system/area is disarmed and will cause an Intruder alarm when the
system/area is armed. The panel will also report a ‘24
-
Hour’ alarm to
the Alarm Receiving Centre when using ‘Contact ID’ reporting.
6 - 24Hr Silent
This zone type will cause a silent alarm if it is activated when the
system/area is disarmed and will cause an Intruder alarm when the
system/area is armed. The panel will also report a ‘24
-
Hour’ Alarm to
the Alarm Receiving Centre when using ‘Contact ID’ reporting.
7 - PA Audible
Normally used for monitoring Panic or hold-up alarms. This zone
type will cause a Panic alarm if it is activated when the system/area is
armed or disarmed.
8 - PA Silent
Normally used for monitoring Panic or hold-up alarms. This zone
type will cause a silent Panic alarm if it is activated when the
system/area is armed or disarmed.
9 - Fire
Normally used for monitoring smoke detectors. This zone type will
cause a Fire alarm with distinctive fire tone if it is activated when the
system/area is armed or disarmed. In addition, the bell output will
pulse.
10 - Medical
This zone type will cause a Silent alarm if it is activated when the
system/area is armed or disarmed. The panel will also report a
Medical alarm to the Alarm
Receiving Centre when using ‘Contact ID’
reporting.
11 - 24Hr Gas
This zone type will cause an Silent alarm if it is activated when the
system/area is armed or disarmed. The panel will also report a 24-
Hour Gas alarm to the Alarm Receiving Centre when usin
g ‘Contact
ID’ reporting.
12 - Auxiliary
This zone type will cause a Silent alarm if it is activated when the
system/area is armed or disarmed. The panel will also report an
Auxiliary
alarm to the Alarm Receiving Centre when using ‘Contact
ID’ reporting.
13 - Tamper
This zone type will cause an Internal alarm if it is activated when the
system/area is disarmed and will cause an Intruder alarm when the
system/area is armed.
14 - Exit Terminator
This zone type is used to finalise the arming procedure when arming
the system/area (see page 62 for details).
15 - Moment Key
This zone type can be used to arm and disarm one or more areas.
When the zone is activated and then secured the areas assigned to the
zone will arm. When the zone is subsequently activated and then
secured the system will disarm the areas assigned to the zone. Tamper
faults will not arm or disarm anything, but will cause a Tamper alarm.
16 - Latch Key
This zone type can be used to arm and disarm one or more areas.
When the zone is activated, the areas assigned to the zone will arm.
When the zone is secured, areas assigned to the zone will disarm.
Tamper faults will not arm or disarm anything, but will cause a
Tamper alarm.
17 - Security
This zone type can be used to Lockout keypads. When the zone is
activated, keypads assigned to the same area will not accept any key
presses. When the zone is secured, all keypads respond as normal.
18 - Omit Key
This zone type will isolate any zone assigned to the same area as
long as it has the ‘Omit’ attribute.
19 - Custom
This zone type can be programmed to operate as required using its
own set of attributes (see page 59 for details).
20 - Conf PA audible
This zone type is for use with multi action PA buttons, or where a
confirmed PA is required, and will activate local sounders.
21 - Conf PA silent
This zone type is for use with multi action PA buttons, or where a
confirmed PA is required, and will not activate local sounders.