HTU Control Registers
1173
SPNU563A – March 2018
Copyright © 2018, Texas Instruments Incorporated
High-End Timer Transfer Unit (HTU) Module
24.4.27 Memory Protection Start Address Register 0 (HTU MP0S)
This register configures the start address of memory protection region 0
Figure 24-40. Memory Protection Start Address Register 0 (HTU MP0S) [offset = 74h]
31
16
STARTADDRESS0
R/WP-0
15
2
1
0
STARTADDRESS0
0
0
R/WP-0
LEGEND: R/W = Read/Write; WP = Write in privilege mode only; -
n
= value after reset
Table 24-40. Memory Protection 0 Start Address Register (HTU MP0S) Field Descriptions
Bit
Field
Description
31-0
STARTADDRESS0
The start address defines at which main memory address the region begins. A memory protection error
will be triggered, if the HTU accesses an address smaller than STARTADDRESS0 and the MPCS
register is configured accordingly. The address is 32-bit aligned, so the 2 LSBs are not significant and
will always read 0.
24.4.28 Memory Protection End Address Register (HTU MP0E)
Figure 24-41. Memory Protection End Address Register (HTU MP0E) [offset = 78h]
31
16
ENDADDRESS0
R/WP-0
15
2
1
0
ENDADDRESS0
0
0
R/WP-0
LEGEND: R/W = Read/Write; WP = Write in privilege mode only; -
n
= value after reset
Table 24-41. Memory Protection End Address Register (HTU MP0E) Field Descriptions
Bit
Field
Description
31-0
ENDADDRESS0
The end address defines at which address the region ends. A memory protection error will be
triggered, if the HTU accesses an address bigger than ENDADDRESS0 and the register bit MPCS
register is configured accordingly. The address is 32-bit aligned, so the 2 LSBs are not significant and
will always read 0. The effective end address is rounded up to the nearest word end address, that is,
0x200 = 0x203.