TESTBOY TV 450
Testing RCD
42
Displayed results:
x1 ........Step 1 trip-out time (
, I
Δ
N, 0º),
x1 ........Step 2 trip-out time (
, I
Δ
N, 180º),
x5 ........Step 3 trip-out time (
, 5
×
I
Δ
N, 0º),
x5 ........Step 4 trip-out time (
, 5
×
I
Δ
N, 180º),
x½ .......Step 5 trip-out time (
, ½
×
I
Δ
N, 0º),
x½ .......Step 6 trip-out time (
, ½
×
I
Δ
N, 180º),
I .........Step 7 trip-out current (0º),
I .........Step 8 trip-out current (180º),
Uc........Contact voltage for rated I
Δ
N.
Notes:
The autotest sequence is immediately stopped if any incorrect condition is
detected, e.g. excessive Uc or trip-out time out of bounds.
Auto test is finished without x5 tests in case of testing the RCD type A with rated
residual currents of I
Δ
n = 300 mA, 500 mA, and 1000 mA. In this case auto test
result passes if all other results pass, and indications for x5 are omitted.
Tests for sensitivity (I
Δ
, steps 7 and 8) are omitted for selective type RCD.