10 

4.4 Polarity Test. 

 

Upon completion of the Earth-Loop Impedance Test, a Polarity 

Test should be conducted so as to confirm that the supply 

system is correctly connected. Place a finger firmly on the 

‘Touch Pad’ (See Figure 6) and maintain pressure for a few 

seconds. The 3 LED’s of the ‘Correct Wiring Indicator’ will 

remain green to indicate correct polarity. Incorrect Polarity is 

indicated by the 3 LED’s intermittently flashing Red. 

 

 

 

Figure 6. 

 

Any failures should be investigated. This will normally be the 

responsibility of the electricity supply company who should be 

advised accordingly. 

 

 

 

 

 

 

 

 

 

Checking the Earth-Loop Impedance will measure the 

resistance of the earth path used by a current flow during a fault 

condition. It will ensure that during any fault condition, the flow 

of electricity to earth will be sufficient to cause the circuit 

protective device e.g. fuse or circuit breaker, to rapidly halt the 

flow of electricity through that circuit. 

 

2. Instrument Overview 

 

Figure 1. 

Correct Wiring Indicator 

Wiring Indicator 

Reference chart 

Voltage Indicator 

Earth - Loop Indicator 

Polarity Test Pad 

Earth-Loop Test Button 

Summary of Contents for TPI 85

Page 1: ...Fax 905 693 0888 email info tpicanada com Test Products International Europe Ltd Longley House International Drive Southgate Crawley West Sussex RH10 6AQ Tel 44 0 1293 530196 Fax 44 0 1293 531870 e ma...

Page 2: ...Conformity In accordance with BS EN ISO IEC 17050 1 We Test Products International Europe Ltd Of Longley House International drive Crawley West Sussex RH10 6AQ declare that Equipment Multi Functional...

Page 3: ...2 Why Measure Earth Loop Impedance 3 Instrument Overview 3 1 Front View 3 2 Top View 3 3 Test Lead 4 Using the Multi Function Earth Loop Tester 4 1 Correct Wiring Indicator 4 2 Voltage Indicator 4 3...

Page 4: ...the resistance and reactance to the flow of an alternating current in an electrical circuit Whereas measuring Resistance to Earth using a digital multi meter will show that there is a good connection...

Page 5: ...ould be investigated This will normally be the responsibility of the electricity supply company who should be advised accordingly Checking the Earth Loop Impedance will measure the resistance of the e...

Page 6: ...dual Current Device RCD employed to protect the circuit under fault condition Recommended Earth Loop Impedance results are detailed in British Standard 7671 IEE Regulations however for guidance the in...

Page 7: ...After confirming correct voltage press and release the Earth Loop Test Switch Button The outer two 1 W 200 W LED s of the Earth Loop Indicator See Figure 5 will illuminate briefly while the test is b...

Page 8: ...sts as soon as it is connected to a live power supply The tests are conducted in the following order 4 1 Correct Wiring Test Connect the instrument to the circuit to be tested and energise the circuit...