43
The calibration and verification of the pulse data necessitates a specialized
measurement equipment arrangement. The IEC standard lays down minimal
requirements.
7 VERIFICATION OF THE PULSE DATA
Teseq uses the following instruments for calibration purposes:
Oscilloscope with >1 GHz bandwidth
Coaxial measurement adapter MD 101 (Pellegrini target as per IEC/EN 61000-4-2)
or MD 103
20 dB attenuator DC-12.4 GHz - SUCOFLEX-HF-coaxial cable
DC-High voltage voltmeter (Ri > 30 GΩ)
The measuring instruments are periodically recalibrated in compliance with
ISO 9001 and ISO 17025.
Ground plane
Ground strap
(pulled away
at its
midpoint)
≥1.2 m
ESD
simulator
Shielded enclosure
for the oscilloscope
and connecting
cables
Current
target
Ground strap
connection point
Power cord
RF filter for
AC power
≥1
.2
m