Form # 1925     Rev. 4/06     TESCOM

GENERAL OPERATION

Continued

2

EXTERNAL FEEDBACK MODE

In External Feedback mode, the ER1200 can
be used to control flow, position, temperature,
or any other variable that can be affected by a
change in pressure. For the purpose of this
operation manual, we will discuss the control
of pressure. In this mode, the ER1200
compares an external feedback signal from a
customer supplied transducer to the setpoint.
Typically, this mode is used when the ER1200
is combined with either a pressure reducing or
back pressure regulator 

(shown with a ratio

actuated, pressure reducing regulator, Figure 2)

.

If the feedback signal is below setpoint, the
ER1200 opens its inlet valve and increases
output pressure. This increases pressure on
the dome of the regulator, opening the main
valve and increasing downstream pressure. If
the feedback is above setpoint, the ER1200
opens its exhaust valve, which decreases
dome pressure, allowing the regulator to
decrease output pressure.

Pressure Connections:

ER1200 inlet pressure is the same as in
internal mode. Refer to regulator installation
and operation instructions and the product
label for maximum inlet pressure information.

Figure 2

Summary of Contents for ER1200 Series

Page 1: ...Feedback Mode 1 External Feedback Mode 2 SPECIFICATIONS 3 ELECTRICAL INSTALLATION 3 4 ER1200 CONFIGURATION Configure Setpoint Signal 5 Configure Analog Output Signal 5 Configure Feedback Signal 5 TUN...

Page 2: ...inlet valve and increases output pressure If the feedback is above setpoint the ER1200 opens its exhaust valve to decrease the output pressure Every 25 milliseconds the feedback is compared to the se...

Page 3: ...either a pressure reducing or back pressure regulator shown with a ratio actuated pressure reducing regulator Figure 2 If the feedback signal is below setpoint the ER1200 opens its inlet valve and inc...

Page 4: ...PSIG Minimum 10 PSIG above desired output pressure Media Clean dry inert gas Environment Temperature 10 F to 150 F Flow Stream Materials 300 Series SST Buna N 6000 Series Aluminum Brass Nickel Silico...

Page 5: ...Form 1925 Rev 4 06 TESCOM 4 Current Setpoint Active Source Voltage Setpoint Current Setpoint Passive Source...

Page 6: ...L MODE JP1 Current Setpoint Mode Install Jumper Voltage Setpoint Mode Remove Jumper RANGE JP2 4 20 mAmp 1 5 Volts Install Jumper on pins 1 2 0 10 Volts Install Jumper on pins 2 3 CONFIGURE ANALOG OUTP...

Page 7: ...sed deadband voltage This can result in drifting of the feedback signal or no response to a small change in setpoint signal Apply a setpoint signal of about 2 5 4 4 mAmps 1 1 VDC if 1 5 VDC or 0 25 VD...

Page 8: ...ystem is experiencing a slow oscillation decrease the gain by rotating the pot counter clockwise until the oscillation stops If the oscillation is rapid increase the reset action by rotating the stabi...

Page 9: ...ressure line The system design has components that can cause a delay in down stream transducer response while the up stream pressure is allowed to build up pressure differential between measurement po...