LIGHT FIXTURE TROUBLESHOOTING (cont’d)
SYMPTOM
CAUSES
CORRECTIVE ACTIONS
SHORT LAMP
Lamp damaged
Check for outer bulb cracks. If air enters outer bulb, arc tube
LIFE
may continue to burn for 100 hours before failure. Check for
bulb cracks where glass meets the base due to tightening lamp
too firmly in socket. Look for broken arc tube or loose metal
parts. Replace lamp.
Improper ballast
Ballast nameplate data should agree with lamp line voltage
and lamp use. If improper ballast is used, the lamp life will be
shortened. A mismatch may also cause the ballast to fail.
LAMP
Improper ballast
Improper ballasting can cause flickering or erratic operation.
FLICKERS AND
In the start-up period the lamp may ignite, start to warm-up
GOES OUT
and then extinguish (cycle).
INTERMITTET
New lamp
Under certain conditions new lamps may “cycle”. Usually
after three (3) tries to start at 30 to 60 second intervals, lamps
will stabilize and operate satisfactorily.
Defective lamp
Replace lamp.
High spike ballast
Ballast produce high spike current. Measure with oscillo-
scope. Replace ballast as required.
60