Operation
26
6.3 MODE SELECTION
NOTE: If a digital input configured to
NOTE: If a digital input configured to
NOTE: If a digital input configured to
NOTE: If a digital input configured to
panel lock
panel lock
panel lock
panel lock is active,
is active,
is active,
is active, changing module modes will not be
changing module modes will not be
changing module modes will not be
changing module modes will not be
possible. Viewing the instruments and event logs is NOT affected by pane
possible. Viewing the instruments and event logs is NOT affected by pane
possible. Viewing the instruments and event logs is NOT affected by pane
possible. Viewing the instruments and event logs is NOT affected by panel lock.
l lock.
l lock.
l lock.
Pressing the
MODE
‘
’
button sets which of the three modes below to leave the controller in.
6.3.1
TEST ON LOAD
Activate by pressing the
MODE
‘
’
button repeatedly until
‘Test on Load’
is shown on the display, then press the
TICK
‘
’
button to confirm the change. An LED indicator beside the button confirms this action.
The
Test on Load
mode will start S2 (if configured as a generator) and transfer the load to S2.
6.3.1.1
STARTING SEQUENCE
As soon as the
MODE
‘
’
is selected and confirmed by pressing the
TICK
‘
’
button is pressed, the output to
give a start signal to an external generator controller is activated (if S2 is configured as a generator)
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm will appear on the display which shows
Fail to
Start.
S2 is seen as available once the supply is within limits (if configured as a mains supply) or had achieved
loading voltage and frequency (if configured as a generator).
6.3.1.2
S2 AVAILABLE
In
Test on Load
mode, the load is automatically transferred to S2 when it is within limits (if configured as a mains
supply) or had achieved loading voltage and frequency (if configured as a generator).
If a start/load request is present but S2 will not go on load, an input configured to
‘S2 Load Inhibit’
could be active.
NOTE:
NOTE:
NOTE:
NOTE: The load transfer signal remains inactive until
The load transfer signal remains inactive until
The load transfer signal remains inactive until
The load transfer signal remains inactive until S2 is seen as available
S2 is seen as available
S2 is seen as available
S2 is seen as available. This prevents
. This prevents
. This prevents
. This prevents loading
loading
loading
loading
to a supply that has failed or is not yet available
to a supply that has failed or is not yet available
to a supply that has failed or is not yet available
to a supply that has failed or is not yet available....
As the load increases and decreases, the module may (depending upon configuration) remove non-essential loads.
This is configured as part of the
Load Shedding
control settings in the Configuration Suite Software.
See section entitled
Load Shedding
elsewhere in this document for further details.
6.3.1.3
STOPPING SEQUENCE
In
Test on Load
mode, S2 will continue to run on load until either:
•
Pressing the
START INHIBIT
‘
’
button to return to start inhibit mode.
•
Pressing the
AUTO
‘
’
button to return to automatic mode.