TCW122B-WD_R2 ( Firmware version 2.xx )
Page 7
Relay can be activated manually or automatically in function of ping:
When manual activation is selected, “Pulse” and “ON/OFF” buttons on “Monitoring” page are active.
The duration of pulse for relay activation can be set from 1 to 253 seconds.
Automatic monitoring page refresh interval can be set from 1 to 253 second. If 0 is chosen - no
automatic refresh.
11.4
Network Setup page
The Network parameters are set on this page. The following parameters can be changed:
Static/DHCP
– IP Address can be static or dynamic (DHCP server should be present in the
network);
IP address, Subnet mask , Default gateway
–
these fields are active if IP address is static;
DNS
– these fields is mandatory, if domain names are used instead of IP addresses. By default
DNS has the same IP address as Default gateway;
Host Name
– up to 16 symbols, it appears as name in DHCP;
MAC
– device MAC address.
The good practice is to change the default IP address of controller immediately after first power-on.
This will avoid collisions if many devices are used in the same network. It may be necessary to clear the arp
cache, each time you connect a new device to the network. This is done by typing
arp -d
in the command
prompt window of computer.
VLAN and MAC address filtering are supported. Up to 3 MAC addresses (including Default Gateway)
can be active in MAC filtering.
Attention!
If you are not familiar with VLAN and MAC filtering leave these sections by default.