2

FAN COIL DESCRIPTION 

AND TROUBLESHOOTING

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installation or servicing system, always turn off main

power to system. There may be more than one disconnect

switch. Turn off accessory heater power if applicable. Lock out

and tag switch with a suitable warning label.

!

WARNING

MULTI

SPEED ECM FAN MOTOR

The multi

speed ECM motor used with this product contains two

parts: the control module and the motor winding section.

A.

It is normal for the motor to rock back and forth on startup. Do

not replace the motor if this is the only problem identified.

B.

If the motor is not running:

1. Check for proper high voltage and ground at the L,G, and N

connections at the motor. Correct any voltage issue before

proceeding to the next step.

2. The motor is communicated through 24

Vac signals to the

1, 2, 3, 4, 5 and C (common) terminals. Verify the part

number of the motor matches the correct replacement motor

part number for the unit model number.

3. Initiate a demand from the thermostat and check the voltage

between C (common) and terminal 1 

 5. If voltage is

present and the motor isn’t operating, then the motor/control

module is failed.

Fan Speed Selection

The fan speed selection is done at the motor connector. Units with

or without electric heaters require a minimum CFM. Refer to the

unit wiring label to ensure that the fan speed selected is not lower

than the minimum fan speed indicated.

Table 1 –  FMC4Z & FMU4Z ECM Motor Speed Taps

Tap

Delay

off

Time(s)

18

24

30

36

Tap 1

90

Default

Tap 2

90

Default

Tap 3

90

Default

Tap 4

90

Default

Tap 5

90

FAN MOTOR

The motor is three

speed direct drive. High

speed lead is black,

medium

speed lead is red, low

speed lead is blue, and common

lead is purple. Be sure proper blower speed has been selected.
The motor is turned on through two different routes. The first

occurs when thermostat calls for the fan in cooling, heat pump, or

fan

only mode. A 24

Vac signal is sent to relay, causing relay to

close its normally open contacts, turning fan on.
The second occurs when there is a call for electric heat. A 24

Vac

signal is sent to heater sequencer/relay, causing it to close, directing

230V through the normally closed contact of fan relay, turning fan

on. The fan remains on until sequencer/relay opens.
If motor does run, test motor for an open winding or a winding

shorted to motor case. If either is present, replace motor.

ELECTRIC HEATER SERVICE

Service can be completed with heater in place. Shut off power

before servicing.

A. Limit Switch

Refer to Electric Heater Kit Function and Troubleshooting section

of this manual.

B. Relay

Refer to Electric Heater Kit Function and Troubleshooting section

of this manual.

C. Transformer

A 40

VA transformer supplies 24

V power for control circuit.

Check for 208/230V on primary side of transformer. If present,

check for 24V on secondary side.

NOTE

:  Transformer is fused. Do not short circuit.

D. Fan Relay

Relay coil is 24

V. Check for proper control voltage. Replace relay

if faulty.

CLEANING OR REPLACING REFRIGERANT
FLOW

CONTROL DEVICE

The FPMAN(C,U) piston can be removed and cleaned if believed

to be plugged. This unit’s piston is unique and replacements are

available from RCD.

The filter drier should be located on the liquid line at the indoor

unit to prevent particulate from plugging the piston.

SEQUENCE OF OPERATION

A.

Condensing Unit

COOLING

When thermostat calls for cooling, the circuit between R and G is

complete and FR is energized. The normally open contacts close

causing blower to operate.
The circuit between R and Y is also complete. This completed

circuit causes contactor in outdoor unit to close which starts

compressor and outdoor fan.
HEATING
When thermostat calls for heating and FAN switch is set on AUTO,

the circuit between R and W is complete. The heater relay is

energized which closes contacts of relay. This completed circuit

energizes all heating elements HTR and blower motor.

B. Heat Pump

COOLING

On a call for cooling, the thermostat makes circuits R

O, R

Y, and

R

G. Circuit R

O energizes reversing valve, switching it to

cooling position. Circuit R

Y energizes contactor starting outdoor

fan motor and compressor. Circuit R

G energizes indoor unit

blower relay starting indoor blower motor.
When thermostat is satisfied, its contacts open de

energizing

contactor reversing valve and blower relay. This stops compressor

and fan motors.
HEATING
On a call for heating, the thermostat makes circuits R

Y and R

G.

Circuit R

Y energizes contactor starting outdoor fan motor and

compressor. Circuit R

G energizes indoor blower relay starting

blower motor.
Should temperature continue to fall, R

W circuit is made through

second

stage room thermostat bulb. Circuit R

W energizes a relay

bringing on supplemental electric heat.

Circuit R

W also energizes the compressor lockout relay which

breaks the R

Y circuit. This prevents the simultaneous operation of

the heat pump and electric heater.

When thermostat is satisfied, its contacts open, de

energizing

contactor and relay. All heaters and motors should stop.

Summary of Contents for FMC4X

Page 1: ...of the Canadian Electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instruction manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal in...

Page 2: ...otor ELECTRIC HEATER SERVICE Service can be completed with heater in place Shut off power before servicing A Limit Switch Refer to Electric Heater Kit Function and Troubleshooting section of this manual B Relay Refer to Electric Heater Kit Function and Troubleshooting section of this manual C Transformer A 40 VA transformer supplies 24 V power for control circuit Check for 208 230V on primary side...

Page 3: ...osed high voltage high current switch When system temperatures cool sufficiently the switch will automatically reset to its closed position Normal failure mode for this switch is open If a limit switch has been determined to be defective NEVER BYPASS THE LIMIT SWITCH When replacing limit switch ensure that it is replaced with a limit switch of identical opening temperature and closing differential...

Page 4: ...ference only Unit may differ in appearance or may not include all components shown A180030 Fig 2 PSC Blower Parts NOTE This illustration is for reference only Unit may differ in appearance or may not include all components shown 1 Control Mounting Plate 3 Time Delay Relay 4 Blower Relay 5 Terminal Block 2 24v Transformer 6 Ground Lug 8 Motor Cover 7 Control Box Cover 9 Heater BlankOff Plate A18002...

Page 5: ...ce or may not include all components shown A180028 Fig 4 Internal Case 4 Header Assy 1 Coil 2 pieces 2 Coil Support Plate Right Side 3 Coil Air Diverter 7 Capillary I 6 Capillary II 5 Distributor 9 Throttle 8 Coil Support Plate Left Side Piston Installed NOTE This illustration is for reference only Unit may differ in appearance or may not include all components shown A180029 Fig 5 Coil Parts ...

Page 6: ...s Use care and wear appropriate protective clothing and gloves when handling parts CAUTION A Air Filter The air filter should be replaced as needed UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage Never operate unit without a filter CAUTION B Cooling Coil Drain Pan and Condensate Drain The cooling coil is easily cleaned when it is dry Inspect coil and clean if neces...

Page 7: ...move control box assembly five screws If there is not enough slack in field wiring high and low voltage it is recommended to disconnect field wiring A13386 Fig 8 Control Box Removal D FPM A B N FMC4X FMU4X Disconnecting the Blower Assembly 1 Disconnect power ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death Before installation or servicing system a...

Page 8: ... disconnected from the unit Be ready to lower the blower assembly CAUTION A13389 Fig 11 Remove Middle Screws E FPM A B N FMC4X FMU4X Servicing the Fan Motor 1 After removing the blower housing from the unit discon nect ground wire from screw on grounding bracket A13390 Fig 12 Disconnect Ground Wire 2 Remove grounding bracket from motor mount assembly At this point the clamp brackets will be loose ...

Page 9: ...ting fluid inside is combustible and may ignite causing burns WARNING 4 Disconnect capacitor leads from capacitor A13393 Fig 15 Capacitor Leads 5 Loosen blower wheel set screws from each motor shaft ac cessing them through the blades of the blower wheels with a Phillips screwdriver A13394 Fig 16 Loosen Blower Set Screw 6 Disconnect one of the blower housings by removing the four housing screws A13...

Page 10: ...move the two middle screws above behind the blower motor that s attached to the top plate 6 Remove the two outer screws that attach the blower support plate to right evaporator coil support See Fig 23 A180034 Fig 23 Remove Outer Screws from Support Plate 7 Remove the top and middle screw of the refrigerant tubing holding bracket See Fig 24 A180035 Fig 24 Remove Top and Middle Screw 8 Bend the hold...

Page 11: ...y After removing the final screw from Step 9 the blower assembly will be completely disconnected from the unit Be ready to lower the blower assembly CAUTION G FMC4Z FMU4Z Servicing the Fan Motor 1 After removing the blower housing from the unit remove grounding bracket from motor mount assembly by remov ing the two screws See Fig 28 29 A180045 Fig 28 Screws Holding the Bracket A180046 Fig 29 Bend ...

Page 12: ...ccessed for cleaning by removing either the control box assembly or the blower assembly Refer to those previous instructions I Removing the Drain Pan 1 Disconnect condensate drains if necessary 2 Remove the four screws located near the corners See Fig 33 3 Lower drain pan from unit A13398 Fig 33 Removing Condensate Pan J Changing the A Coil 1 Disconnect power 2 Disconnect field wiring low and high...

Page 13: ...ide of the fan coil unit in line with the liquid refrigerant line FPMAN C U Fan coils are shipped with a piston metering device designed for the most common outdoor unit matches The piston included with the fan coil is unique to this product and cannot be replaced with the piston shipped with the outdoor unit Refer to AHRI ratings to check if your combination can use the piston shipped with the un...

Page 14: ...P D 7310 W Morris St D Indianapolis IN 46231 Edition Date 03 18 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No SM FPMA 03 Replaces SS FPMA 02 ...

Reviews: