13
A13400
Fig. 35
−
Top Plate and Insulation
10. Remove the two insulation support brackets.
A13401
Fig. 36
−
Insulation Support Brackets
11. On bottom of unit, remove the eight screws attaching the
condensate baffle assembly to the side coil supports.
A13402
Fig. 37
−
Condensate Baffle Screws
12. Remove condensate baffle assembly.
A13403
Fig. 38
−
Remove Condensate Baffle Assembly
K. Refrigerant Metering Device
The refrigerant metering device is located on the side of the fan coil
unit, in
−
line with the liquid refrigerant line .
FPMAN(C,U) Fan coils are shipped with a piston metering device
designed for the most common outdoor unit matches. The piston
included with the fan coil is unique to this product and cannot be
replaced with the piston shipped with the outdoor unit. Refer to
AHRI ratings to check if your combination can use the piston
shipped with the unit or requires an accessory TXV.
FPMBN(C,U), FMC4X, FMU4X, FMC4Z, FMU4Z Fan Coils are
shipped with a TXV metering device.
Use two wrenches to remove the nut from the piston body or to
remove the TXV.
A13404
Fig. 39
−
Metering Device Location / Piston (FPMA Units)