background image

FMA4X, FMA4P: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

5

3. Use  UL  listed  conduit  and  conduit  connector  for  connecting

line-voltage leads to unit and obtaining proper ground. If conduit

connection uses reducing washers, a separate ground wire must be

used. Grounding can also be accomplished by using the ground lug

provided  in  the  control  box.  Power  wiring  may  be  connected  to

either  the  right  or  left  sides  or  top  of  unit.  Knockouts  of  7/8"

(22 mm) dia. are provided for connection of power wiring to unit.

Some  heater  sizes  may  require  a  conduit  larger  than  the  7/8"

opening;  in  this  situation  the  high-voltage  connection  opening

should be enlarged to fit the conduit.

When  removing  the  knockouts  for  electrical  connections,  an

opening in the insulation should be cut to fit the opening. The cut

edge of the insulation should be reinforced with foil tape to prevent

fraying. The foil facing and insulation shall not be removed beyond

the knockout opening size.

4. Install  plastic  grommet  packed  with  unit  in  hole  for  low-voltage

wires.

5. Connect  low-voltage  leads  to  thermostat  and  outdoor  unit.  See

Fig. 6

 and 

Fig. 7

 as well as the outdoor unit wiring label. 

Select Proper Blower Speed 

Before  operating  unit,  be  sure  that  the  proper  blower  speed  has  been

selected. Fan speeds are selected manually. 

To change the fan speed on model FMA4P:

• Factory default fan speed is medium; fan-motor red wire connected to

fan relay No. 4.

• For high speed, connect fan-motor black wire to fan relay No. 4.

• For low speed,  connect fan-motor blue wire  to fan relay No. 4 and

fan-motor red wire to fan relay No. 6.

• Always  connect  the  unused  fan-motor  wire  to  the  dummy  terminal

block.

• When selecting the proper airflow, refer to 

Table 4

 below to choose

proper blower speeds for cooling and heating.

To change the fan speed on model FMA4X:

• At the motor connection plug connect the green wire to the desired

motor tap number indicated on the motor plug (

Fig. 8

)

• For the electric heat fan speed selection connect the white wire to the

desired motor tap number indicated on the motor plug. See 

Table 2

 for

factory default settings.

TXV (FMA4X Only)

NOTE: 

The TXVs are preset at the factory and do not need adjustment

for reliable operation.

START-UP

Refer  to  outdoor  unit  Installation  Instructions  for  system  start-up

instructions and refrigerant charging method details.

SEQUENCE OF OPERATION

NOTE: 

The following sequence of operation is based on units installed

with  PSC  motor  and Time  Delay  Board  (TDB).  For  units  with  ECM

motor,  the  off-delay  is  programmed  into  the  motor.  Follow 

Table 2

,

ECM Motor Speed Taps & the corresponding blower off delays for each

speed tap.

CONTINUOUS FAN

Thermostat closes R to G. G energizes and completes circuit to indoor

blower motor. When G is de-energized, there is a 90’s blower off-delay.

COOLING MODE

Thermostat energizes R to G, R to Y, and R to O (heat pump only). G

energizes and completes indoor blower motor. Y energizes outdoor unit

(O  is  energized  for  heat  pump).  When  cooling  call  is  satisfied,  G  is

de-energized, there is a 90s blower off-delay.

HEAT PUMP HEATING MODE

Thermostat  energizes  R  to  G  and  R  to Y.  G  energizes  and  completes

circuit  to  indoor  blower  motor.  When  heating  call  is  satisfied,  G  is

de-energized, there is a 90s blower off-delay.

HEAT PUMP HEATING WITH AUXILIARY 

ELECTRIC HEAT

Thermostat  energizes  R  to  G,  R  to Y,  and  R  to W1.  G  energizes  and

completes  circuit  to  indoor  blower  motor.  W1  energizes  electric  heat

relay(s)  which  completes  circuit  to  heater  element(s).  When  W1  is

de-energized,  electric  heat  relay(s)  open,  turning  off  heater  elements.

When G is de-energized there is a 90s blower off-delay.

ELECTRIC HEAT OR EMERGENCY HEAT MODE

Thermostat energizes R to W1. W1 energizes electric heat relay(s) which

completes  circuit  to  heater  element(s).  Blower  motor  is  energized

through  normally  closed  contacts  on  fan  relay.  When  W1  is

de-energized, electric heat relay(s) opens, there is no blower off-delay,

(units with ECM motor will have blower off-delay based on motor speed

tap selection).

CARE AND MAINTENANCE

For  continuing high performance and  to minimize  possible  equipment

failure,  it  is  essential  that  periodic  maintenance  be  performed  on  this

equipment. The only required maintenance that may be performed by the

consumer is filter maintenance. See 

Table 3

.

The  minimum  maintenance  requirements  for  this  equipment  are  as

follows:

1. Inspect and clean or replace air filter each month or as required.

2. Inspect cooling coil, drain pan, and condensate drain each cooling

season for cleanliness. Clean as necessary.

3. Inspect  blower motor and wheel for cleanliness each heating and

cooling season. Clean as necessary.

4. Inspect electrical connections for tightness and controls for proper

operation each heating and cooling season. Service as necessary.

NOTE: 

The installing technician should explain system operation to the

consumer with particular emphasis on indoor fan coil operation sounds

and filter maintenance.

Table 2 – FMA4X ECM Motor Speed Taps

Tap

Delay-off 

Time (s)

19

25

31

37

Tap 1

30

-

-

-

-

Tap 2

90

Default

-

Default

-

Tap 3

30

-

-

-

-

Tap 4

90

-

Default

-

Default

Tap 5

30

-

-

-

-

Table 3 – Filter Sizes

Unit Size

Filter Size In. (mm)

18, 24

16x20x1 (406x508x25)0

30, 36

20x20x1 (508x508x25)

Summary of Contents for FMA4X

Page 1: ...installed in unconditioned space NOTE Nuisance sweating may occur if the unit is installed in a humid location with low airflow Units are designed for upflow applications only Local codes may limit this free air return type unit to installation in single level applications INSTALLATION Check Equipment Unpack unit and move to final location Remove carton taking care not to damage unit Remove protec...

Page 2: ...into place install refrigerant tubing as follows 1 Route tubing to connection points taking care not to block service access 2 Remove plugs from liquid and vapor lines 3 Braze connections using either silver bearing or non silver bearing brazing material Do not use soft solder materials which melt below 800 F 427 C Consult local code requirements Always flow nitrogen through the system refrigerant...

Page 3: ...r NOTE Unit is intended for non ducted return air applications Product Data sheet includes a list of accessories including louvered wall panels and return air opening grills If ducted return is used airflow must meet criteria established in the Product Data Local codes may limit this unit to single level applications Design the duct system in accordance with ACCA Manual 0 Design for Residential Wi...

Page 4: ...sured along low voltage wire use No 16 AWG color coded insulated 35 C minimum wire A13092 Fig 5 Transformer Connections NOTE Before proceeding with electrical connections make certain that voltage frequency and phase correspond to that specified on rating plate Also check to be sure that the service provided by utility is sufficient to handle additional load imposed by this equipment Refer to unit...

Page 5: ...motor and Time Delay Board TDB For units with ECM motor the off delay is programmed into the motor Follow Table 2 ECM Motor Speed Taps the corresponding blower off delays for each speed tap CONTINUOUS FAN Thermostat closes R to G G energizes and completes circuit to indoor blower motor When G is de energized there is a 90 s blower off delay COOLING MODE Thermostat energizes R to G R to Y and R to ...

Page 6: ...t metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing safety glasses and gloves when handling parts WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death Disconnect all power to unit before servicing field wires or removing control package The disconnect when used on access panel does not allow safe servi...

Page 7: ...92 530 Med 845 801 759 716 675 626 573 510 Low 676 640 602 563 523 499 FMA4P3000AL High 1367 1312 1252 1192 1131 1063 990 908 821 Med 1211 1165 1114 1065 1016 960 899 833 748 Low 992 952 912 873 828 782 728 656 627 FMA4P3600AL High 1397 1345 1290 1263 1196 1116 1051 980 907 Med 1298 1252 1198 1147 1094 1037 976 910 842 Low 1149 1105 1056 1008 960 909 856 791 726 Table 5 ECM Airflow Performance Sta...

Reviews: