F97CMN and G97CMN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
36
A12325
Fig. 43 – Ventilated Combustion Air and Non-Direct Vent Termination Clearance
NOTE:
The following is based upon National codes for gas appliances and is provided as a reference.
Refer to local codes which may supersede these standards and/or recommendations.
>
greater than,
≥
greater than or equal to,
<
less than,
≤
less than or equal to
8. Avoid venting under a deck or large overhang. Recirculation could occur and cause performance or system problems. Ice build-up may occur.
Item
Clearance Description
Canadian Installations
(1 )
(per CAN/CSA B149.1)
U.S. Installations
(2 )
(per ANSI Z223.1/NFPA 54)
A
Clearance above grade, veranda, porch, deck,
balcony or anticipated snow level
12 in. (305 mm)
18 in. (457 mm) above roof surface.
12 in. (305 mm)
B
Clearance to a window or door that may be
opened
12 in. (305 mm) for appliances >10,000 BTUh (3 kW)
and </=100,000 BTUh (30 kW),
36 in. (914 mm) for appliances >100,000 BTUh (30 kW)
4ft. (1.2M) below or to the side of the opening,
1 ft (.3M) above the opening.
Manufacturer’s Recommendation: See Note 8.
C
Clearance to a permanently closed window
For clearances not specified in ANSI Z223.1/NFPA 54 or CAN/CSA B149.1, clearances shall be in accordance
with local installation codes and the requirements of the gas supplier and the manufacturer’s installation
instructions.
Manufacturer’s Recommendation: See Notes 3-8.
D
Vertical clearance to a ventilated soffit located
above the terminal within a horizontal distance of 2
feet (61 cm) from the centerline of the terminal
E
Clearance to an unventilated soffit
F
Clearance to an outside corner
G
Clearance to an inside corner
H
Clearance to each side of the centerline extended
above electrical meter or gas service regulator
assembly
3 ft. (.9 M) within 15 ft. (4.6 M)
above the meter/regulator assembly.
3 ft. (.9 M) within 15 ft. (4.6 M)
above the meter/regulator assembly.
I
Clearance to service regulator vent outlet
3ft. (.9 M)
See Note 4.
J
Clearance to non-mechanical air supply inlet to
building or the combustion air inlet to any other
appliance
12 in. (305 mm) for appliances >10,000 Btuh(3 kW)
and </= 100,000 BTUh (30 kW),
36 in. (914 mm) for appliances >100,000 BTUh (30 kW)
4ft. (1.2M) below or to the side of the opening,
1 ft (.3M) above the opening.
Manufacturer’s Recommendation: See Note 8
K
Clearance to a mechanical air supply inlet
6 ft. (1.8 M)
3ft. (.9 M) above if within 10 ft. (3 M) horizontally
L
Clearance under a veranda, porch, deck, or
balcony
12 in. (305 mm).
Permitted only if veranda, porch, deck, or balcony is fully
open on a minimum of two sides beneath the floor.
See Note 4.
Manufacturer’s Recommendation: See Notes 3-8.
M
Clearance to each side of the centerline extended
above or below vent terminal of the furnace to a
dryer or water heater vent, or other appliance’s
direct vent intake or exhaust
12 in. (305 mm)
12 in. (305 mm)
N
Clearance to a moisture exhaust duct
(dryer vent, spa exhaust, etc.)
12 in. (305 mm) See Note 4
12 in. (305 mm) See Note 4
0
Clearance from a plumbing vent stack
3 ft. (.9 M)
3 ft. (.9 M)
P
Clearance above paved sidewalk or paved
driveway located on public property
7 ft. (2.1 M).
Vent shall not terminate above a sidewalk or paved driveway
that is located between two single-family dwellings and
serves both dwellings.
7ft. (2.1M)
Notes:
1. In accordance with the current CAN/CSA B149.1, Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
3. NOTE: This table is based upon National codes for gas appliances, and are provided as a reference.
Refer to Local codes which may supersede these standards and/or recommendations.
4. For clearances not specified in ANSI Z223.1/NFPA 54 or CAN/CSA B 149.1, clearances shall be in accordance with local installation codes and the requirements of the gas supplier and
the manufacturer’s installation instructions.
5. When locating vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation of the combustion products of adjacent
vents. Recirculation can cause poor combustion, inlet condensation problems, vent termination icing, and/or accelerated corrosion of the heat exchangers.
6. Design and position vent outlets to avoid ice build-up on and moisture damage to surrounding surfaces.
7. The vent for this appliance shall not terminate:
a. Near soffit vents of crawl space vents or other areas where condensate or vapor could create a nuisance or hazard or property damage; or
b. Where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.
8. These National standards apply to all non-direct-vent gas appliances. Contact Local code officials for additional requirements and/or exclusions.
V
V