General
Table 1: Physical data
Unit size
25 ton
30 ton
40 ton
50 ton
60 ton
70 ton
80 ton
Compressor data - standard capacity, standard efficiency
Quantity/size
(nominal HP)
1/4.5, 1/7, 1/10
1/5.5, 1/7,
1/7, 1/7.5
1/5.5, 1/8.5,
1/10, 1/11.5
1/7.5, 1/10,
1/11.5, 1/15
1/12, 1/12,
1/15, 1/15
1/10, 1/15,
1/15, 1/20
1/15, 1/15,
1/15, 1/20
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Capacity steps
7
11
15
15
8
9
7
Number of circuits
2
2
2
2
2
2
2
Compressor data - high capacity, standard efficiency
Quantity/size
(nominal HP)
1/5, 1/7.5, 1/10
1/5.5, 1/7,
1/7, 1/ 8.5
1/7, 1/13,
1/8.5, 1/10
1/8.5, 1/15,
1/7.5, 1/15
Type
Scroll
Scroll
Scroll
Scroll
Capacity steps
7
11
15
11
Number of circuits
2
2
2
2
Compressor data - standard capacity, high efficiency
Quantity/size
(nominal HP)
1/5, 1/7.5, 1/13 1/7, 1/7, 1/18.5 1/7.5, 1/7.5,
1/10, 1/13
1/10, 1/10,
1/12, 1/17.5
1/10, 1/15,
1/15, 1/17.5
1/13, 1/15,
1/15, 1/27
1/15, 1/15,
1/15, 1/27
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Capacity steps
15–100%
15–100%
15–100%
15–100%
15–100%
15–100%
15–100%
Number of circuits
2
2
2
2
2
2
2
Supply fan
Quantity of fans/
motors
1/1
1/1
1/1
1/1
2/2
2/2
2/2
Type
Direct drive
plenum
Direct drive
plenum
Direct drive
plenum
Direct drive
plenum
Direct driven
plenum
Direct driven
plenum
Direct driven
plenum
Size (in.)
27
27
33
33
27
27
27
Motor size range each
fan (min to max HP)
5–25
5–25
10–50
10–50
5-30
5-30
5-30
Airflow range (min to
max CFM)
5,000–12,000
5,000–12,000
8,000–20,000
8,000–20,000 12,000-24,000 14,000-32,000 14,000-32,000
Total static pressure
range (min to max iwg)
1.0–8.0
1.0–8.0
1.0–8.0
1.0–8.0
1-8.3
1-8.3
1-8.3
Return fan
Quantity of fans/
motors
1/1
1/1
1/1
1/1
1/1
1/1
1/1
Type
Belt-driven
plenum
Belt-driven
plenum
Belt-driven
plenum
Belt-driven
plenum
Direct driven
plenum
Direct driven
plenum
Direct driven
plenum
Size (in.)
27
27
30
30
33
33
33
Motor size range (min
to max HP)
5–10
5–10
5–20
5–20
7.5-40
7.5-40
7.5-40
Airflow range (min to
max CFM)
5,000–12,000
5,000–12,000
8,000–20,000
8,000–20,000 12,000-24,000 14,000-32,000 14,000-32,000
Total static pressure
range (min to max iwg)
0.5–3.0
0.5–3.0
0.5–3.0
0.5–3.0
0.5–3.0
0.5–3.0
0.5–3.0
Exhaust fan
Quantity of fans/
motors
1/1
1/1
1/1
1/1
1/1
1/1
1/1
Type
Belt-driven
forward curved
Belt-driven
forward curved
Belt-driven
forward curved
Belt-driven
forward curved
Belt-driven
forward curved
Belt-driven
forward curved
Belt-driven
forward curved
Size (in.)
18–18
18–18
25–25
25–25
30-30
30-30
30-30
Motor size range (min
to max HP)
3–15
3–15
5–20
5–20
5-25
5-40
5-40
Tempmaster
®
Omni™ Premier 25 Ton to 80 Ton Rooftop Units Installation and Maintenance Guide
9
Tempmaster