Figure 43: Original discharge panel location
Figure 44: New discharge panel location
Component
Description
A
Gasket to be applied to
the fixed panel
Air hoods
The rooftop unit can be ordered with several
options that utilize hoods over outside and exhaust
air openings.
The unique design of these hoods allows them to be
installed on the unit at the factory. They are folded
flat for ease of shipping. By removing the hold-down
brackets, the hoods can be easily unfolded and
assembled in the field with minimal effort.
Refer to Figure 45 and Figure 46, which details the
removal of the hold-down brackets and securing the
side pieces to the hood.
Outside air hood
Note:
The 25 ton to 30 ton units only have two
hoods. The 40 ton to 80 ton units have three
hoods, as shown in Figure 45.
1. Remove the hold-down brackets from the
air hoods (one on each side of each hood).
There will be either four or six total hold-down
brackets depending on the number of hoods.
2. Lift up the hood top, and open out the side
hood pieces.
3. Attach each side hood piece to its hood top
using the shipped loose screws.
4. Repeat steps 2 and 3 for the remaining hood
tops and their side hood pieces.
Tempmaster
®
Omni™ Premier 25 Ton to 80 Ton Rooftop Units Installation and Maintenance Guide
83