TemperZone OSA 200RKTV Installation & Maintenance Download Page 1

OSA 200RKTV

Reverse Cycle R410A

Split System Outdoor Unit

Installation &

Maintenance

Line Lengths

The standard unit allows for a line length  
up to 30 m. For line lengths between 30 m 
and 60 m, refer to 

temperzone

's 

Split Systems Installation Guide (refer  
www.temperzone.biz/Technical Support)
.
Refer also to Oil Charge overleaf. 
Maximum line length when extended is 60m.

Height Separation Limits

Outdoor Unit above Indoor Unit :  20 m
Outdoor Unit below Indoor Unit :  20 m

Vertical Risers

If the outdoor unit is to be installed above 
the indoor unit, then the suction riser should 
be trapped at the bottom of the vertical 
rise and then again at 8 m (maximum) 
intervals. This is to ensure oil return to the 
compressor. The trap to be a 'swan neck' 
curve in the pipe, with no change in the pipe 
size.

Piping

1.  Use clean sealed refrigeration grade 

piping and accessories designed 
specifically for R410A.

2.   Cut pipe with a pipe cutter ONLY.
3.   Use long radius bends (2x pipe dia.).
4.   Insulate the suction (gas) line and seal 

all insulation joints.

5.  Filter dryers are not required or recom-

mended, however extreme care must be 
taken to keep the piping system dry.

6.  Include a process point in the 

interconnecting pipework.

7.  Ensure open pipe ends are sealed until 

the final connection is made.

8.  Immediately before removing brazed 

pipe connection's seal, reduce holding 
charge between connection points and 
service valves to atmospheric pressure. 

Warning

:  Failure to do so may cause 

injury.

Charging

The unit is supplied with refrigerant 
HFC-410A (R410A) which is sufficient 
for 10 m of pipework between the indoor 
and outdoor units; refer wiring diagram 
specification table for amount.  Add, or 
subtract, 60 g of HFC-410A per metre to suit 
the installed line length.
Procedure:
1.  Evacuate Indoor Unit and 

interconnecting pipework to a pressure 
of 500 microns and hold for 15 mins. 

2.  Add refrigerant, if needed, via the 

Schraeder connection on the smaller of 
the Outdoor Unit's two service valves. 

Drain

Four drain holes are provided in the base.  
Three plastic bungs are supplied (loose) 
should you want to direct the condensate 
and/or rain water to one of the holes 
provided. Drain connection adaptors (25/13) 
are available as an optional extra.

REFRIGERATION PIPING
General

The OSA 200 is shipped with a refrigerant 
charge sufficient for a 10 m line length; 
refer wiring diagram specification table 
for amount. The matched indoor unit is 
shipped with a holding charge of nitrogen. 
OSA 200 units have shut-off service valves 
and swaged assemblies. Two loose pipe 
extensions are supplied to enable a choice 
of exit – side or rear; both require brazing. 

Recommended Pipe Sizes

Suction pipe : 

22 mm OD

Liquid pipe : 

13 mm OD

GENERAL

This OSA 200RKTV Outdoor Unit must be 
installed in accordance with all national and 
local safety codes.

Options 

1. Anti-vibration mounts (rubber)
2. Drain connection adaptors - right angle.

INSTALLATION
Positioning

Refer to dimension diagram below for 
minimum clearances. 
Fasten the unit down to a firm flat horizontal 
base using the four holes provided in the 
mounting rails. To avoid tranfer of vibration, 
mount the unit on the optional rubber 
mounts available from 

temperzone

.

When the unit is being installed on a roof 
it is recommended that the unit is installed 
on a substantial structure with vibration 
isolating springs or rubber mounts (optional 
extra) beneath the unit. These items are not 
supplied with the unit.

Dimensions (mm) 

      OSA 200RKTV

PROJECTION

Not to Scale

Net Weight 142 kg

ACCESS

PANEL

1210

OVERALL

822 MTG CTR

12 DIA. HOLE + SLOT

150 MIN.

 CLEARANCE

2000 MIN. CLEARANCE

500 MIN. CLEARANCE

500 MIN.

 CLEARANCE

25 ID

DRAIN

HOLES

25 ID

DRAIN

HOLES

590 MTG CTR

630

OVERALL

REFRIG.

CONN'S

EXIT

620

186

186

1130

OVERALL

30 ID

ELECTRICAL

CONDUIT

HOLES

ALTERNATIVE

CONN'S

EXIT

16