background image

OPA 650RKTB

Packaged Reverse Cycle R410A

Air Cooled Air Conditioner

GENERAL

This OPA 650RKTB Outdoor Unit must be 
installed in accordance with all national and 
local safety codes.

CONFIGURATIONS

The OPA 650RKTB is supplied in one of 
two standard configurations :
1.  Horizontal supply/return air with box 

mounting channel (RKTBH), or

2.  Downward supply air with box mounting 

channel (RKTBU).

REFRIGERATION SySTEm
General

The OPA 650 has two independent 
refrigeration circuits and two compressors 
to provide the flexibility and economy of 
two stage operation, i.e. utilising one or 
two circuits as conditions vary, plus the 
advantage of staggered starting.

Each refrigeration system has been 
charged with 9.5 kg each of HFC-410A 
(R410A) refrigerant. Tapping points are 
provided to measure discharge and suction 
operating pressures.  

Compressors

The compressors are directional scroll 
type. The compressor lubricant is polyol 
ester oil (POE). Note, this oil absorbs 
moisture quickly if exposed to open air. 
On commissioning, the compressors must 
be checked for correct rotation (refer Start 
Up Procedure). A time delay prevents 
simultaneous starting of the compressors.

ECONOmISER (Option)

If the outdoor air temperature or heat 
content preferably, is below that of the 
return air the fresh air damper opens and 
the return air damper closes to provide the 
first stage of cooling. A spill air facility in 
the building may be necessary for when 
the return air damper is closed. The fresh 
air damper should return to minimum 
setting and the return air damper open 
before compressors are allowed to operate 
to provide further cooling. A low limit 
thermostat is fitted to prevent compressors 
operating with a mixed air-on coil 
temperature below 18°C; resets at 20°C. 
This is by-passed during heating mode.

INSTALLATION
Positioning

Refer to dimension diagrams for minimum 
clearances. If multiple units are to be 
placed side-by-side then allow at least 2 m 
between coil faces.

Installation & 

maintenance

mounting

The unit should be fastened to a firm flat 
horizontal base using the holes supplied in 
the mounting channels.
When the unit is being installed on a roof it is 
recommended that the unit is installed on a 
substantial structure with vibration isolating 
springs beneath the unit. These springs are 
not supplied with the unit. 
Flexible duct connections are recommended 
between the supply and return ducts and 
the unit.

Condensate Drain

The condensate drain should be 'U' trapped 
outside the unit. The trap should have a 
vertical height of at least 100 mm. The drain 
should have a slope of at least 1 in 50 and 
must not be piped to a level above the unit 
drain pipe (refer Fig. 3).

Electrical Requirements

Electrical work must be done by a qualified 
electrician.  The outdoor unit must be wired 
directly from a distribution board by means 
of a circuit breaker or H.R.C. fuse, and a 
mains isolator provided - preferably close to 
the unit.

Note

:  DO NOT USE REWIRABLE FUSES.

The OPA 650 is provided with a 24V AC 
control circuit for a thermostat, on/off switch 
and/or time clock.
The control transformer 240V primary 
voltage is used for countries with 230-240V 
power supply. For countries with supply 
voltages 200-220V, change the primary 
voltage on the transformer to 208V.
Standard units are suitable for use with 
thermostats with either manual Heat/Cool 
selection or automatic changeover subject to 
the contact ratings of the thermostats. 
A 24 hour power supply to the compressor 
crank case heaters is required, otherwise the 
warranty is void.

CHECK TESTS

1. Leave the on/off switch in the off position 

and close the mains isolating switch.  
A four hour delay period is required to 
allow the crankcase heaters to drive any 
liquid refrigerant out of the compressor oil. 
Bypass the crankcase heater thermostat 
(CCHT) for this period only.

2. Check that the shipping blocks beneath 

each compressor have been removed 
and that each compressor is secure on its 
mounts.

3. Check that all fan motors are free running.
4. Check that the thermostat is correctly 

wired to the unit and is set at the desired 
temperature.

5. Check that the air filters have been 

correctly installed if fitted.

6. Check air diffuser dampers are open if 

appropriate.

START UP PROCEDURE

Use the supplied Commissioning Sheet to 
help you complete the following procedure:
1. After the four hour delay period has 

expired, switch on the unit. Ensure the 
crankcase heater thermostat has been 
reconnected.

2. Check the supply voltage between each 

phase and neutral.

3. Compressors fitted are directional. Check 

for correct rotation. If rotation is incorrect 
the compressor will not pump, be noisy, 
and will draw minimal current. To correct 
motor rotation, change the phasing at 
the main power terminal. If changing the 
phasing, check the indoor air fan then 
runs in the correct direction also.

4. Measure the current draw on each phase 

to the compressor motors and measure 
the current draw of each fan motor.  
Check all readings against the specified 
values in the wiring diagram.

5. Fit R410A compatible gauges and 

measure the suction and discharge 
pressures of both refrigeration circuits.

6. Check that the outdoor air fan motors are 

running smoothly.

7. Test the operation of the reversing valve 

by running the unit in both the heating 
and cooling mode.

8. Check the indoor unit's fan belt tension 

after 20 mins of operation and adjust if 
necessary (refer Commissioning Sheet).

9. Check the supply air flow at each outlet.
10.Check the tightness of all electrical 

connections and sign the check label.

11.Touch up any outdoor unit paintwork 

damage to prevent corrosion.

SETTING SUPPLy AIR FLOW

Consult OPA 650 Technical Data pamphlet 
for details of airflow/duct static pressure, if 
required. 
If the indoor air returning to the unit is 
regularly expected to be above 50%RH, 
then the coil face velocity should be limited 
to be 2.5 m/s or less (refer Air Handling 
graph in Technical Data pamphlet). 
High humidity levels can occur in tropical or 
subtropical conditions, and/or when heavily 
moisture laden fresh air is introduced. 
Select a fan speed that avoids water carry-
over problems.
In a free blow or low resistance application,  
beware of exceeding the fan motor's full 
load amp limit (refer wiring diagram).

Reviews: