TemperZone ISD 840K Installation & Maintenance Download Page 1

ISD 840K, 950K

Ducted Split System

Indoor Units

Installation &

Maintenance

GENERAL
These ISD indoor units are designed to be 
coupled with their respective OSA outdoor 
units.  Units must be installed in accordance 
with all national and local safety codes.
 
Combinations
One ISD 840K with one  OSA 840RKTB
One ISD 950K with one  OSA 950RKTB
 
Option
TZT-701 or SAT-2 Thermostat
Filters

INSTALLATION
Unpacking
The unit's supply air spigot has been 
secured inside the unit for ease of shipping. 
Remove the spigot and secure it in place 
using the existing screws.

Positioning & Mounting
Provide sufficient clearance to the access 
panels.

Mount on a suitable level platform using 
vibration isolators. Access to fixing centres 
beneath the return air spigot can be made 
via the removeable bungs in the spigot's 
base.

Condensate Drain
The unit has an internal sloping condensate 
drain tray. The trap should have a vertical 
height of at least 100 mm.  The drain should 
have a slope of at least 1 in 50 and must not 
be piped to a level above the unit drain tray 
(refer Fig.2).

For long condensate pipe runs, fit a vent 
pipe near the drain trap. The top of the vent 
pipe must be at least 100 mm above the ISD 
unit's drain tray. 

It is essential that the drainage system 
for the evaporator is checked by pouring 
water in the drain tray and seeing that it 
discharges at the end of the drain and does 
not overflow the drain tray.

INDOOR-OUTDOOR UNIT CONNECTIONS
Refer to the relevant OSA Outdoor Unit 
'Installation & Maintenance' pamphlet for 
piping instructions.  For wiring connections, 
refer to the Outdoor Unit wiring diagram.

REFRIGERATION PIPING
Pipe Connection Sizes
 & Type
Liquid : 

16 mm OD (

5

/

8

") sweat

Suction :  35 mm OD (

11

/

8

") sweat

The ISD is shipped from the factory with 
a pressurised holding charge of nitrogen.  
Immediately before removing any brazed 

Fig.1   Dimensions (mm)

Not to Scale

   

Net

   

Weight

  ISD 840K  372 kg
  ISD 950K  383 kg

Fig. 2

NOTE
The manufacturer reserves the right to 
change specifications at any time without 
notice or obligation.  Certified dimensions 
available on request. 

CORNER LOADS (kg)

MODEL 

Z

ISD 840K  70 

116  116  70

ISD 950K  66 

137  125  55

OPEN

DRAIN

MINIMUM

SLOPE

20 mm PER m

(1 IN 50)

100 mm

MINIMUM

200 mm

APPROX.

'U' TRAP

100 mm

APPROX.

VENT PIPE

FOR LONG

CONDENSATE

DRAIN RUNS

Condensate Drain

PROJECTION

2005

2220 OA

75

75

DRAIN 28 OD

150

60

1320 OA

W

X

Y

Z

REFRIG.

CONN’S

1000 MIN. CLEARANCE

1360

MOUNTING CENTRES

105

430

500 MIN. CLEARANCE

REFRIGERANT

CONNECTIONS

ELECTRICAL

BOX

ACCESS PANEL

FILTER ACCESS

EITHER SIDE

VERTICAL

DISCHARGE

MODEL

ELECTRICAL

ACCESS

PANEL

A

B

470

565

830

305

470

535

MODEL 

B

ISD 840K  1070  955
ISD 950K  1280  1165