ISD 840K, 950K
Ducted Split System
Indoor Units
Installation &
Maintenance
GENERAL
These ISD indoor units are designed to be
coupled with their respective OSA outdoor
units. Units must be installed in accordance
with all national and local safety codes.
Combinations
One ISD 840K with one OSA 840RKTB
One ISD 950K with one OSA 950RKTB
Option
TZT-701 or SAT-2 Thermostat
Filters
INSTALLATION
Unpacking
The unit's supply air spigot has been
secured inside the unit for ease of shipping.
Remove the spigot and secure it in place
using the existing screws.
Positioning & Mounting
Provide sufficient clearance to the access
panels.
Mount on a suitable level platform using
vibration isolators. Access to fixing centres
beneath the return air spigot can be made
via the removeable bungs in the spigot's
base.
Condensate Drain
The unit has an internal sloping condensate
drain tray. The trap should have a vertical
height of at least 100 mm. The drain should
have a slope of at least 1 in 50 and must not
be piped to a level above the unit drain tray
(refer Fig.2).
For long condensate pipe runs, fit a vent
pipe near the drain trap. The top of the vent
pipe must be at least 100 mm above the ISD
unit's drain tray.
It is essential that the drainage system
for the evaporator is checked by pouring
water in the drain tray and seeing that it
discharges at the end of the drain and does
not overflow the drain tray.
INDOOR-OUTDOOR UNIT CONNECTIONS
Refer to the relevant OSA Outdoor Unit
'Installation & Maintenance' pamphlet for
piping instructions. For wiring connections,
refer to the Outdoor Unit wiring diagram.
REFRIGERATION PIPING
Pipe Connection Sizes & Type
Liquid :
16 mm OD (
5
/
8
") sweat
Suction : 35 mm OD (
11
/
8
") sweat
The ISD is shipped from the factory with
a pressurised holding charge of nitrogen.
Immediately before removing any brazed
Fig.1 Dimensions (mm)
Not to Scale
Net
Weight
ISD 840K 372 kg
ISD 950K 383 kg
Fig. 2
NOTE
The manufacturer reserves the right to
change specifications at any time without
notice or obligation. Certified dimensions
available on request.
CORNER LOADS (kg)
MODEL
W
X
Y
Z
ISD 840K 70
116 116 70
ISD 950K 66
137 125 55
OPEN
DRAIN
MINIMUM
SLOPE
20 mm PER m
(1 IN 50)
100 mm
MINIMUM
200 mm
APPROX.
'U' TRAP
100 mm
APPROX.
VENT PIPE
FOR LONG
CONDENSATE
DRAIN RUNS
Condensate Drain
PROJECTION
2005
2220 OA
75
75
DRAIN 28 OD
150
60
1320 OA
W
X
Y
Z
REFRIG.
CONN’S
1000 MIN. CLEARANCE
1360
MOUNTING CENTRES
105
430
500 MIN. CLEARANCE
REFRIGERANT
CONNECTIONS
ELECTRICAL
BOX
ACCESS PANEL
FILTER ACCESS
EITHER SIDE
VERTICAL
DISCHARGE
MODEL
ELECTRICAL
ACCESS
PANEL
A
B
470
565
830
305
470
535
MODEL
A
B
ISD 840K 1070 955
ISD 950K 1280 1165