TemperZone ISD 80K Installation & Maintenance Download Page 1

ISD 80/95/110/140 K-DN  

(c/w SAT-2 Controller)

Ducted Split System

Indoor Units

Installation &

Maintenance

GENERAL
These ISD

S

K-DN indoor units are designed 

to be coupled with the OSA

S

RK outdoor 

units. The '-DN' indicates the unit is supplied 
complete with SAT-2 room temperature 
controller and safety drain tray.
Units must be installed in accordance with 
all national and local safety codes.

 

Combinations
One ISD 81K with one  OSA 80RKS
One ISD 95K with one  OSA 95RKS
One ISD 110K with one  OSA 110RKS
One ISD 110K with one  OSA 110RKT
One ISD 140K with one  OSA 140RKT

Options
1.  Filter Box c/w polypropylene net filter
2.  Spring Mounting Kit
3.  Electric Heater Box
4.  Supply & Return Air Plenums
5.  SAT-2 Accessories (refer overleaf). 

SAFETY DRAIN TRAY
The unit is supplied with a safety drain tray 
to protect your ceiling against accidental 
damage. The safety drain tray is best 
secured to the ISD unit 

after the unit has 

been suspended in the ceiling, however it 
is possible to fit it 

before if circumstances 

make this easier.

AIR FILTRATION / FILTER BOX (Option)
As air filtration requirements vary, filters are 
not supplied with the unit. Filters should 
ideally be installed on the return air side of 
the unit, no closer than 500mm from the 
back of the unit and easily accessible for 
cleaning. To maximise the efficiency of air 
flow, the return air filter should be twice the 
area of the ISD unit's return air spigot/s.  If 
efficiency is less of a concern a Filter Box is 
available.

The Filter Box is installed by unscrewing 
the return air spigot and replacing it with 
the Filter Box's filter-integrated spigot. The 
filter may be accessed from either side of 
this spigot. This new spigot has a depth of 
135 mm, instead of 60 mm. 

ELECTRIC HEATER BOX (Option)
The Electric Heater Box is installed by 
unscrewing the supply air spigot and 
replacing it with the Electric Heat Box's 
element-integrated spigot. This new spigot 
has a depth of 195 mm, instead of 60 mm. 
A separate page of installation instructions is 
supplied with the Kit. 

INSTALLATION
Positioning & Mounting
Provide 500 mm minimum clearance to both 
ends of the unit. 

Fig. 1  Dimensions (mm)

Not to Scale

PROJECTION

ISD 80K, 91K, 110K, 140K

Fig. 2  Spring Mounting

Fig. 3  Solid Mounting

RECOMMENDED

MOUNTING

SYSTEM

(OPTIONAL

EXTRA)

Fig. 4

OPEN

DRAIN

MINIMUM

SLOPE

20 mm PER m

(1 IN 50)

50 mm

MINIMUM

100 mm

APPROX.

'U' TRAP

100 mm

APPROX.

VENT PIPE

FOR LONG

CONDENSATE

DRAIN RUNS

UNIT

Note: The Safety Drain Tray 

does not require trapping.

REFRIGERANT

CONNECTIONS

E

OVERALL

50

420 OA

225

335

60

30

DRAIN 19 OD

30

650 OA

400

482

MOUNTING

CENTRES

B

ELECTRICAL

CONDUIT HOLE

(BOTH ENDS)

60

60

FAN ACCESS VIA

REMOVEABLE BASE

 & DRAIN TRAY

ACCESS

PANEL

ELECTRICAL

BOX

170

ELECTRICAL

BOX

C

FIXED MTG CTRS

D

500 MIN. CLEARANCE

500 MIN. CLEARANCE

F

Condensate Drain

Net Weight

ISD 80K    36 kg

  ISD 91K    39 kg

ISD 110K   40 kg

ISD 140K   46 kg

TIGHTEN 

LOCKNUTS

FOR 

STRENGTH

MOUNTING ROD

MOUNTING

BRACKETS

SUPPLIED

B

125
175
240
240

A

570
660
787
787

C

747
836
962
962

MODEL

ISD 80K
ISD 95K

ISD 110K
ISD 140K

D

805
895

1020
1020

E

835
925

1050
1050

F

190
230
290
290