TemperZone ISD 250Q Installation & Maintenance Download Page 1

ISD 250Q, 300Q – 470Q

Ducted Split System
Indoor Units

Installation &
Maintenance

GENERAL

These ISD indoor units are designed to be
coupled with their respective OSA outdoor
units.  Units must be installed in
accordance with all national and local
safety codes.

Combinations

One ISD 250Q with one  OSA 240RA
One ISD 250Q with one  OSA 250
One ISD 300Q with one  OSA 290RA
One ISD 300Q with one  OSA 300
One ISD 390Q with one  OSA 390
One ISD 390Q with one  OSA 410RA
One ISD 470Q with one  OSA 480

Options

1.  Filter Box.
2.  Spring Mounting Kit
3.  Electric Heat Kit.

FILTER BOX (Option)

The Filter Box is installed by unscrewing
the return air spigot and replacing it with
the Filter Box's filter-integrated spigot. The
filter may be accessed from either side of
this spigot. This new spigot has a depth of
150 mm, instead of 65 mm.

ISD c/w ELECTIC HEAT OPTION
(Factory Fitted)

Units supplied with electric boost heat are
designed to conform to AS/NZS 3350.2.40
1997.
ISD 250Q–390Q:  3 x 3 kW elements
ISD 470Q:  3 x 4 kW elements

Note

:  Reverse Cycle systems fitted with

electric heat require an Outdoor Unit low
limit t/stat (supplied separately).

UNPACKING UNITS

In an area adjacent to the installation site
remove from the ISD unit from its carton
and examine it carefully for any damage
which may have occurred in transit. Record
any damage on the carrier's delivery
documents and refer the matter
immediately to the manufacturer's nearest
Sales Office.

INSTALLATION
Positioning & Mounting

Provide 500 mm minimum clearance to the
electrical panel. If the filter box option is to
be used, allow adequate clearance for the
two half length filters to be withdrawn from
either side of the unit.

If low noise is a critical factor in the
installation, refer to Figure 6 for noise
isolation recommendations.

It is recommended that the unit be mounted
using the spring mounting system, supplied
as an optional extra (Fig.3). This system
minimises transfer of vibration into the
building structure.

Fig.1   Dimensions (mm)

Not to Scale

ELECTRICAL

ACCESS PANEL

REFRIGERANT
CONNECTIONS

F

A

OVERALL

H

MOUNTING CENTRES

G

80

DRAIN 28 OD

E

C

688

OPTIONAL

SPRING MTG

CENTRES

ELECTRICAL

CONDUIT HOLES

65

65

B

OVERALL

735 OA

FAN ACCESS VIA

REMOVEABLE BASE

 & DRAIN TRAY

ACCESS

PANEL

W

X

Y

Z

D

600

MOUNTING

STRAP

CENTRES

J

K

Net

Weight

ISD 250Q  120 kg
ISD 300Q  120 kg
ISD 390Q  175 kg
ISD 470Q  182 kg

MODEL

A

B

C

D

E

F

G

H

J

K

ISD 250Q

1625

575

975

300

240

1375

425

1518

125

325

ISD 300Q

1625

575

975

300

240

1375

425

1518

125

325

ISD 390Q

1680

700

1030

310

365

1430

555

1573

125

325

ISD 470Q

2060

700

1525

310

299

1705

555

1915

170

165

Fig. 2

Note

:  The manufacturer reserves the right to change specifications at any

time without notice or obligation.  Certified dimensions available on request.

CORNER LOADS (kg)

W

X

Y

Z

29

35

31

25

29

35

31

25

37

41

32

35

41

50

50

41

MODEL

ISD 250Q

ISD 300Q

ISD 390Q

ISD 470Q

OPEN
DRAIN

MINIMUM
SLOPE
20 mm PER m
(1 IN 50)

50 mm
MINIMUM

100 mm

APPROX.

'U' TRAP

100 mm

APPROX.

VENT PIPE
FOR LONG
CONDENSATE
DRAIN RUNS

UNIT

Condensate Drain

PROJECTION