ISD 220Q, 265Q
Ducted Split System
Indoor Units
Installation &
Maintenance
GENERAL
The ISD 220Q indoor units are designed to
be coupled with the OSA 220 outdoor units.
The ISD 265Q indoor units are designed to
be coupled with the OSA 265 outdoor units.
Units must be installed in accordance with
all national and local safety codes.
Options
1. Filter Box.
2. Spring Mounting Kit
3. Electric Heater Box.
FILTER BOX (Option)
The Filter Box is installed by unscrewing
the return air spigot and replacing it with
the Filter Box's filter-integrated spigot. The
filter may be accessed from either side of
this spigot. This new spigot has a depth of
135 mm, instead of 60 mm.
ELECTRIC HEATER BOX (Option)
The Electric Heater Box is installed by
unscrewing the supply air spigot and
replacing it with the Electric Heater Box's
element-integrated spigot. This new spigot
has a depth of 195 mm, instead of 60 mm.
A separate page of installation instructions
is supplied with the Kit.
UNPACKING UNITS
In an area adjacent to the installation site
remove from the ISD unit from its carton
and examine it carefully for any damage
which may have occurred in transit. Record
any damage on the carrier's delivery
documents and refer the matter
immediately to the manufacturer's nearest
Sales Office.
INSTALLATION
Positioning & Mounting
Provide 500 mm minimum clearance to the
electrical panel. If the filter box option is to
be used, allow adequate clearance for the
two half length filters to be withdrawn from
either side of the unit.
If the Electric Heat Kit option is to be used,
allow adequate clearance for servicing.
If low noise is a critical factor in the
installation, refer to Figure 6 for noise
isolation recommendations.
It is recommended that the unit be mounted
using the spring mounting system, supplied
as an optional extra (Fig.2). This system
minimises transfer of vibration into the
building structure.
If a more rigid installation can be tolerated,
then suspend the unit from four threaded
rods (not supplied) and use locknuts (not
supplied), as shown in Figure 3.
Fig. 1
Dimensions (mm)
Not to Scale
PROJECTION
NOTE
The manufacturer reserves the right to change
specifications at any time without notice or
obligation. Certified dimensions available on
request.
Fig. 2 Spring Mounting
Fig. 3 Solid Mounting
TIGHTEN
LOCKNUTS
FOR
STRENGTH
MOUNTING FLANGE
MOUNTING ROD
RECOMMENDED
MOUNTING
SYSTEM
(OPTIONAL
EXTRA)
1185
ELECTRICAL
ACCESS PANEL
REFRIGERANT
CONNECTIONS
80
230
15
B
630 OA
MOUNTING
SLOTS 20 x 9
530
HANGING
CENTRES
865
595
OPTIONAL
SPRING MTG
CENTRES
165
ELECTRICAL
CONDUIT HOLES
60
60
1365
OVERALL
1240
HANGING CENTRES
DRAIN 19 OD
FAN ACCESS VIA
REMOVEABLE BASE
& DRAIN TRAY
ACCESS
PANEL
1285
SPRING MTG CTRS
A
OVERALL
C
ISD 220Q, 265Q
B
15
85
A
425
555
C
350
500
MODEL
ISD 220Q
ISD 265Q
Net Weight
74 kg
93 kg