RJ-45 Jack Pin Assignments
Jack
Connects To
Pin Assignment
Function
Status LED Reference
Black
Digital Dialer
input/output
of host alarm
panel.
1 = Brown R1
2 = Blue
4 = Green R (Ring)
5 = Red T (Tip)
7 = Orange
8 = Gray T1
Connects alarm
panel to TG-7FP
for transmitting
alarms to
central station.
If PPF is ENABLED,
STC LED 2 will flash 7
times when alarm panel
is not detected and
PPF enabled.
DC Terminal Strip Pin Assignments
Terminal
Strip Pin
Definition
Connects To
Function
Note
1 GND
2 DC
Power
input
Regulated
12VDC or
24VDC Source
Powers up the
communicator
Consumption rates vary
based on input voltage used
Main Terminal Strip Pin Assignments
Terminal
Strip Pin
Definition
Connects To
Function
Status LED
Reference
1 STC2
2 STC2
Supervisory Relay
Trip output for
programmable
trouble conditions.
Normally Closed.
24-hour trip
zone input
on alarm
panel.
Enables transmission of
programmed supervisory
trouble code (see diagram
or installation section).
STC LED 2
3 STC1
4 STC1
Supervisory Relay
Trip output for
programmable
trouble conditions.
Normally Open.
24-hour trip
zone input
on alarm
panel.
Enables transmission of
programmed supervisory
trouble code (see diagram
or installation section).
STC LED 2
5 GND
Trip Ground
External trip
relay.
Allows an external relay to
trigger an alarm signal.
LED 7
6 IN
Trip Input
External trip
relay.
Allows an external relay to
trigger an alarm signal.