SensoMAG  B12L/U Fire Base - 

Installation Manual

Senso

MAG

 

B12L/U is an alarm base (12V) with relay output. The base has 

two operation modes: Latch and Unlatch. The base is compatible with 
conventional detectors SensoMAG series: F10, F10B, R20, S30 and M40 for 
applications in security alarm systems.

Operation modes

The operation mode is set with a jumper on the relay module (over the 
terminals of the PCB). The description of the operation modes is:

Latch Mode - 

In case of FIRE signal the relay will be switched on until the 

AUX power supply if off. After switching on the AUX power supply the detector 
will be reset.

Unlatch Mode - 

In case of FIRE signal the relay will be switched on for 7-9 

seconds. After that time the detector will be reset automatically.

18020765

, RevC, 06/2015

Power Supply. . . . . . . . . . . . . . . . . . . . . . 10-15V
Consumption in stand-by mode . . . . . . . . <50µA 
Consumption in FIRE mode. . . . . . . . . . . <25mA
Reset time in Unlatch operation mode. . . 7 - 9 sec
Relay terminals . . . . . . . . . . . . . . . . . . . . 30V/0.5A

2

Wire Gauge for terminals. . . . . . . . . . . . . 3.0mm
Operating temperature. . . . . . . . . . . . . . . -10

°

C to +60

°

C

Relative humidity resistance . . . . . . . . . .

(93

 ± 3)%

 @

 40°

C

Weight . . . . . . . . . . . . . . . . . . . . . . . . . . .

~

46g

Dimensions . . . . . . . . . . . . . . . . . . . . . . . 102x11mm
Material (plastic), color. . . . . . . . . . . . . . . ABS, white

Technical & Environmental Specifications

General Description

Connection Diagram

Intruder 

Alarm Panel

B12L/U

B12L/U

+12V

+12V

Relay Terminals

Jumper for Latch/Unlatch 
operation mode

Unlatch Mode - 

The jumper is 

removed.

Latch Mode - 

The jumper is set.

NOTE: The base comes with factory 
set jumper, i.e the 

Latch operation 

mode is set by default.