22
Functional Description
2 s
2 s
1 s
1 s
30 s
Siren
Com-
mands
Pre-alarm
Main alarm
"Emergency"
output
Reset
alarms
With "Stop emergency" off and O + I (switch
off/on)
"Active emergency" trigger
Active emergency sequence
To trigger "Active emergency", press the stop and emergen-
cy call switch
First the pre-alarm (2 s sound, 2 s pause) and after 30 s the
main alarm (1 s sound, 1 s pause) through the siren; status
LED blinks green rapidly (battery charged).
Already activated commands (e. g. pull drum) are switched
off; other dangerous commands are blocked.
If you turn the stop and emergency call switch, new com-
mands are accepted again; however, the alarm continues.
On expiry of the pre-alarm time, the "Emergency" output is
switched (e. g. for activating an emergency-call transmission
device).
By turning the stop and emergency call switch and then
switching off and on the transmitter, you can reset the
alarm during the pre-alarm and the main alarm.
The "Siren" output is not monitored with the factory
setting; but it can be parameterized to be monitored.