Getting Started
Teledyne ML – T101 Operation Manual
38
S
PA
N
C
A
L
Z
E
R
O
C
A
L
S
PA
N
C
A
L
Z
E
R
O
C
A
L
CONTROL IN
A B C D E F U
+
CONTROL IN
A B C D E F U
+
-
+
Local Power Connections
External Power Connections
5 VDC Power
Supply
Figure 3-10. Control Input Connector
Table 3-6. Control Input Signals
INPUT #
STATUS
DEFINITION
ON CONDITION
A
REMOTE ZERO CAL The analyzer is placed in Zero Calibration mode. The mode
field of the display will read ZERO CAL R.
B
REMOTE
LO SPAN CAL
The analyzer is placed in low span calibration mode as part
of performing a low span (midpoint) calibration. The mode
field of the display will read LO CAL R.
C, D, E & F
SPARE
Digital Ground
The ground level from the analyzer’s internal DC power
supplies (same as chassis ground)
U
External Power
input
Input pin for +5 VDC required to activate pins A – F.
+
5 VDC output
Internally generated 5V DC power. To activate inputs A – F,
place a jumper between this pin and the “U” pin. The
maximum amperage through this port is 300 mA (combined
with the analog output supply, if used).
Summary of Contents for T101
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ...ii This page intentionally left blank ...
Page 10: ...vi This page intentionally left blank ...
Page 12: ...viii This page intentionally left blank ...
Page 22: ...TABLE OF CONTENTS Teledyne ML T101 Operation Manual xviii This page intentionally left blank ...
Page 166: ...Remote Operation Teledyne ML T101 Operation Manual 162 This page intentionally left blank ...
Page 248: ......
Page 336: ...This page intentionally left blank B 4 07266B DCN6485 ...
Page 339: ...APPENDIX D Wire List and Electronic Schematics D 1 07266B DCN6485 ...
Page 340: ...This page intentionally left blank 07266B DCN6485 D 2 ...
Page 345: ...D 7 07266B DCN6485 ...