background image

Quick Start Guide 

System Controllers 

 

PAGE 1 OF 2 

214629 REV -  RA 7327 

Teledyne Paradise Datacom 

offers a robust family of 

system controllers which can be used for remote moni-
tor and control of both indoor rack-mountable systems 
and outdoor systems. 

The 1RU Redundant System Controllers include the 
RCP2-1100, used with 1:1 redundant systems, and the 
RCP2-1200, used with 1:2 redundant systems. 

The FPRC-1100 system controller is used with 1:1 
fixed phase combined systems, and the FPRC-1200 is 
used with 1:2 fixed phase combined systems. 

Rack Mounting 

The system controller may be installed in a standard 
IEC 19” equipment cabinet. The controller is available 
with optional rack slides. Follow the rack slide manu-
facturer’s instructions on installation of the slide rails 
into the equipment cabinet. Secure the front panel of 
the controller to the cabinet frame mounting rails using 
10-32x0.5 pan head screws, #10 flat washer and #10 
nylon washer (placed against the surface of the unit). 

Cable Connections 

The primary connection between the controller and the 
LNA/LNB switch plate or SSPA switch assembly is 
through Port J3. This connector is a 23-pin circular MIL 
connector, type MS3112E16-23S. A standard 100 ft. 
(30m) cable is typically used to connect between Port 
J3 of the controller and the switch plate assembly. 

Providing Prime Power 

Most controllers are fitted with removable AC power 
supply modules which connect to a 110V power outlet 
using the supplied IEC power cords. A DC input option 
is also available. 

Local Communication 

All Teledyne Paradise Datacom system controllers 
share a common local menu structure, which is de-
tailed in the Operations Manual. Settings for Communi-
cation, Operation, Fault Setup, Options and Calibration 

may all be selected from the front panel menu. Operat-
ing conditions are also available for review in the 2x40 
front panel display. 

The Local/Remote key selects whether the 
controller is operational by front panel 
(local) control or by remote control. Remote 
control includes both the rear panel parallel 
control signals as well as the serial com-
munication. 

The Auto/Manual key selects between available 
switching Modes. In Auto mode, a unit failure will result 
in automatic switching of the system’s transfer switch-
es. In manual mode a unit failure will result in fault 
alarms but no switchover will occur. 

The front panel signal path mimic display provides a 
visual representation of the redundant system block 
diagram. Green LEDs indicate the position of the 
transfer switches showing the RF signal path from the 
RF input to the RF output. 

When in Local Mode, the operator may select which 
unit in the redundant system is transmitting to the RF 
output by pressing the appropriate Unit # key on the 
signal path mimic display. 

Fault indicator LEDs illuminate RED when 
the corresponding fault condition occurs. 
There are fault lights for Summary, Unit 1, 
Unit 2, and Power Supply faults. The RCP2-
1200 and FPRC-1200 also includes a fault 
light for Unit 3. 

Remote Communication 

The controller offers a wide range or remote communi-
cation capability, including serial interface over RS485 
or RS232, and an Ethernet interface which supports 
IPNet, SNMP and a HTTP web interface. Parallel 
alarm contacts are also available.  

See the Operations Manual for a complete description 
of the remote control interface, including the serial 
communication protocol. 

The main serial port, J4, is used for remote connection 
with any host computer. This port contains both RS-
232 and RS-485 communication in half duplex. A set 

RCP2-1100 Redundant System Controller 

Reviews: