OLCT 60
FIXED POINTGAS MONITOR
USER MANUAL
NPO60GB
Revision F.2
15
GD10P
OLCT60
1
(+24Vdc)
3
(+24Vdc)
2 (0V)
2 (0V)
3
(mA)
1
(mA)
4 (not used)
4 (not used)
5 (not used)
N/A
Figure 20: wiring the OLCT 60D/GD10P.
Ensure the specificity of the numbering between GD10P and the OLCT 60D.
2.7.7
Detector grounding
Connect the enclosure ground points to earth according to the regulations with a 4mm² (11
AWG) wire.
The OLCT 60 features an internal ground point as well. The internal grounding shall be preferred
as the primary equipment ground.
028
Figure 21: OLCT 60 grounding
2.7.8
Closing the cover
Before connecting the OLCT 60 to the controller, the cover shall be tightly closed. Firmly tighten
the locking screw as well (see Figure 16, page 13).