
ADFM® Flow Meter
Section 2 Setup and Installation
2-46
2.9 Insertion: Current HTI
These instructions refer to
Figure
2-49 on the following page.
The preferred locations for sensor installation in a horizontal
pipe are between the clock positions 1 and 5, and 7 and 11, as
shown in Figure 2-49. Installation at the top and bottom of the
pipe should be avoided due to the possibility of trapped air or
sedimentation. The sensor may be installed at any position in a
vertical pipe, provided the stream is flowing upward.
For all other variations in position or flow, contact Teledyne Isco
for assistance.
Tools and supplies
Installation of the Hot Tap requires the following user-provided
tools and supplies:
• Tapping saddle, thread-o-let, or spool piece
• 2" NPT Corporation stop or ball valve
•
3
/
16
" hex screwdriver
• Pipe wrench
• PTFE pipe thread tape
• Optional cable conduit (min. 2" dia.)
The standard length of the Hot Tap sensor cable is 50 ft (15m). A
custom-length cable can be up to 100 ft (30m). If conduit is used,
a minimum ID of 2 in. is required. Minimum bend radius for the
cable is 6 in.
Dimensional requirements
When determining the installation location, consider the
minimum clearance required for installation and removal of the
sensor from the pipe. The minimum clearance required is found
by calculating the dimension
C
.
For the standard length sensor, the distance from the top of the
valve to the inner pipe wall (
D
) must not exceed 15" in order to
have an
insertion depth of up to 1
1
/
2
" past the inner pipe wall.
Note
Typical insertion depth is usually between
1
/
4
in. and
1
/
2
in. However, installations in pipes where buildup of grease
or debris is expected, deeper insertion will ensure unimpaired
flow readings.
I f
D
e x c e e d s 1 5 i n c h e s, a c u s t o m l e n g t h s e n s o r s h a f t
(part #60-5314-677) must be ordered. Contact Teledyne Isco for
assistance with custom length selection.
Summary of Contents for ADFM Hot Tap
Page 2: ......
Page 4: ......
Page 20: ...ADFM Flow Meter Section 1 Introduction 1 10 ...
Page 85: ...ADFM Flow Meter Section 2 Setup and Installation 2 65 Figure 2 73 Viewing data in Expert View ...
Page 86: ...ADFM Flow Meter Section 2 Setup and Installation 2 66 ...
Page 98: ...ADFM Flow Meter Section 3 Maintenance and Troubleshooting 3 12 ...
Page 114: ......
Page 116: ......