MULTIXPLO AND MULTITOX DETECTORS
OPERATING MANUAL
18
NOSP17665
Revision 02a
4.2.4
Magnets identification
The magnets are identified by two stickers “PG1” and “PG2” fixed on the housing.
4.3
Electric Connection
Never adjust electrical connections when detectors are powered. Maintenance
must be undertaken by qualified staff. Observe safety site rules.
The MultiXplo and MultiTox are sensors with standard current output 4-20mA or 0-22mA. The
connection can be on 3 or 4 wires. The 4 wires configuration allows insulation between the signal
and power loops.
We recommend using an armoured and shielded cable, type NF M 87 202, in accordance with
the requirements for hazardous areas and NF C 15 100. Other cables can be used if they are
compliant with the local regulations and standards.
The table below shows the maximum cable lengths based on the wire cross section and the supply
voltage delivered by the detection unit.
Min. single wire cross section mm²/AWG 0.5 (20)
0.9 (18)
1.5 (16)
2.5 (13)
Supply voltage 24VDC
288 m
505 m
893 m
1000 m
Supply voltage 24VDC -10%
173 m
303 m
536 m
926 m
NB: Those values are calculated for a minimum supply voltage of 18VDC at the sensor level and
for the maximum consumption of the detector (5W)
PG2
PG1
Summary of Contents for Everywhereyoulook DG-TT7-K
Page 18: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 12 NOSP17665 Revision 02a...
Page 34: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 28 NOSP17665 Revision 02a...
Page 58: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 52 NOSP17665 Revision 02a...
Page 66: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 60 NOSP17665 Revision 02a...
Page 68: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 62 NOSP17665 Revision 02a...
Page 69: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a 63...
Page 70: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 64 NOSP17665 Revision 02a...
Page 71: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a 65...