Page 3-31
For one of the mounting screws, include a ground lug and star washer. (Use one ground lug
with #14 AWG stranded wire per chassis.)
NOTE:
Ground each shelf of an LCX Fiber Splice/Patch Combination Panel separately.
5. Install adapter packs and/or special function modules in configurable LCX Fiber Patch Pan-
els. Figure 35 shows a 6-adapter pack being installed in a 4RU LCX Fiber Configurable Patch
Panel. Push in the quick-connect plungers at both ends of the faceplate to lock the pack or
module in the bulkhead.
6. Place a plastic cabling ring at each of the four corners of the chassis, as shown in Figures 36
and 37. You can add and move the rings around later during cabling. The rings not only serve
as corrals for fiber cable but also as guideposts. You can insert cables in the split rings or
route them around the rings.
Plunger at Top & Bottom
of Patch Plates
Figure 35 - Installing Adapter Pack & Special Function Modules
Figure 36 - Inserting Cabling Rings
Plastic Cabling Rings