Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel

Power

 :: 009-8005-0404 :: 009-8005-0404G :: 009-8005-0404L :: 

009-1000-1033RE (End of Life June 30, 2015)

 

Installation Guide

Applies to

:  009-8005-0404, 009-8005-0404G, 009-8005-0404L, and 009-1000-1033RE 

(End of Life June 30, 2015)

Fuse Alarm Panel - 009-8005-0404

Front view

Fuse Alarm Panel - 009-8005-0404G 

Front view

Fuse Alarm Panel - 009-8005-0404G 

Rear view

Fuse Alarm Panel - 009-8005-0404

Rear view

Summary of Contents for 009-8005-0404

Page 1: ...4G 009 8005 0404L 009 1000 1033RE End of Life June 30 2015 Installation Guide Applies to 009 8005 0404 009 8005 0404G 009 8005 0404L and 009 1000 1033RE End of Life June 30 2015 Fuse Alarm Panel 009 8005 0404 Front view Fuse Alarm Panel 009 8005 0404G Front view Fuse Alarm Panel 009 8005 0404G Rear view Fuse Alarm Panel 009 8005 0404 Rear view ...

Page 2: ... 1 Model 009 8005 0404 1 Figure 2 Model 009 8005 0404G 1 Figure 3 Bracket Orientation 5 Figure 4 Rack Mounting 5 Figure 5 Ground Lug Connection 6 Figure 6 Input Lugs 6 Figure 7 Disengaging a TPA Fuse Holder 7 Figure 8 Alarm Indicators 009 8005 0404 7 Figure 9 Alarm Reference Card and Terminals 009 8005 0404 8 Figure 10 Alarm Indicators 009 8005 0404G 9 Figure 11 Power Alarm Terminals 009 8004 0404...

Page 3: ...Nominal Voltage 24Vdc 48Vdc Max input load rating 200A per side Nominal power loss at full load 70W per side 9600W full load per side 200Ax48V Percentage of full load power dissipation at nominal voltage Less than 1 Max input interrupt device 250A Short circuit withstand rating 5000A GMT 450A Input terminal studs with split ring lock washers nuts for dual hole compression lugs Dual 1 4 20 studs on...

Page 4: ...use rating Grounding Specifications Earth GND Terminal Studs with split ring lock washers hex nuts for dual hole compression lug Dual 1 4 20 threaded holes on 5 8 in 1 59 cm centers Torque supplied bolt using 7 16 in or 12 mm socket to 45 in lb 5 N m Ground Wire Size Up to 4 AWG depends on input interrupt device Alarms Specifications Alarm Relay Contacts 2A 30 Vdc 0 6A 60 Vdc Max Alarm Card Power ...

Page 5: ...ng 14 lb 6 kg 24 lb 11 kg model 009 8005 0404L Weight shipping 15 lb 7 kg 26 lb 12 kg model 009 8005 0404L Environment Specifications Operating Temperature Range at 200A 009 8005 0404 009 8005 0404G 009 8005 0404L 10 C 14 F to 55 C 131 F 5 C 12 F to 50 C 122 F 10 C 14 F to 35 C 95 F at 225A Hardware is included for flush or extended mounting in 19 or 23 relay racks Due to it s depth and weight mou...

Page 6: ...ct is damaged please report it to the carrier and contact Telect Quality ALERT Elevated Operating Ambient Temperature If you install the rack in a closed or multi unit rack assembly the operating ambient temperature of the rack environment may be greater than room ambient Therefore take care to install the equipment in an environment compatible with the maximum operating temperature Reduced Air Fl...

Page 7: ...ounting panel as high as possible on the rack Due to the depth and weight of model 009 8005 0404L mounting rails should be used to support the mounted panel in the rack 3 Tighten the screws to 35 in lb 4 29 N m 4 Loosen you need not remove two screws securing the rear terminal cover on the back of the panel 5 Remove the cover 6 Use a listed approved crimping tool to attach a listed approved dual h...

Page 8: ...ibution unit PDU before connecting this panel s input cables to the PDU Figure 5 Ground Lug Connection 11 For input wiring wiring used as inputs to this distribution panel crimp dual hole compression lugs onto 8 AWG to 4 0 AWG copper wires Insulate lug barrels with UL94 V 0 rated heat shrink tubing 12 Clean the terminals and lugs with a nonabrasive nonmetallic pad 13 If required lightly coat anti ...

Page 9: ...tive all plastic slugs If necessary pull out the TPA carrier about an inch from its holder to disengage the TPA fuse as shown in Figure 7 For 009 8005 0404 and 009 8005 0404L alarm indica tors continue at step 17 For 009 8005 0404G alarm indicators go to step 22 17 Enable the fuse or breaker at PDU 250A max to turn on Feed A to Side A and then check voltage and polarity at input connectors of pane...

Page 10: ...he panel Expect an open circuit Ω between Terminals C and NC Expect continuity 0Ω between Terminals C and NO 19 Also test the fuse alarm relay contacts at the FUSE ALARM terminals on the rear of the panel For both the VIS visual and AUD audible indicator contacts Expect continuity 0Ω between Terminals C and NC Expect an open circuit Ω between Terminals C and NO 20 Repeat Steps 17 through 20 to pow...

Page 11: ...alarm terminals Figure 10 Alarm Indicators 009 8005 0404G 22 Enable the fuse or breaker at PDU 250A max to turn on Feed A to Side A Also enable fuse or breaker at PDU 250A max to turn on Feed B to Side B Check voltage and polarity at input connectors of panel Also check that POWER ON A LED on front of panel turns on green FUSE ALARM LED must be off POWER ON B LED on front of panel turns on green F...

Page 12: ... load at each output terminal 28 Tighten the nuts to 20 in lb 2 3 N m 29 Connect the other end of the output wire to load 30 For GMT output wiring use 20 to 12 AWG copper wire Work with one wire at a time At the panel end of the wire either Crimp a single hole ring or fork lug as required by NEC or Strip 3 8 in 1 cm of insulation for a bare wire connection 31 Clean the panel terminals and lug if a...

Page 13: ...rrier and insert the operable fuse as shown in Figure 14 For a GMT fuse pull out the dummy fuse and insert the operable fuse as shown in Figure 15 Test the power and polarity at the input of each equipment load ALERT GMT fuses have a small inherent electrical resistance resulting in a small inherent power loss For this reason the GMT fuse manufacturer recommends that the load for GMT fuses up to a...

Page 14: ... Re install operable TPA fuse before proceeding Likewise replace one of the operable GMT fuses with a blown fuse to verify that the FUSE ALARM LED and FUSE ALARM terminals are also as specified above Re install the operable GMT fuse before proceeding 38 If desired connect the remote external audio visual alarm indicator wires solid or tinned wires 26 to 20 AWG to the PWR ALARM and FUSE ALARM termi...

Page 15: ...9 15A 124820 20A 124821 25A 125244 30A 122734 40A 122738 50A 122739 TPA Fuse Holder 146010 GMT Fuses 1 2A Red RED 004001 3 4A Brown BRN 004008 1A Gray GRY 100991 1 1 3A White WHT 004006 1 1 2A White Yellow WHT YEL 004011 2A Orange ORN 004002 2 1 2A Orange White ORN WHT 130783 3A Blue BLU 004012 3 1 2A White Blue WHT BLU 130782 4A White Brown WHT BRN 004013 5A Green GRN 004014 71 2A Black White BLK...

Page 16: ...E Die Code 37 LCD1 0 14B X Die Code 42 LCD2 0 14B X Die Code 45 LCD3 0 14B X Die Code 50 Table 2 Ground Lugs 1 4 in Dual Holes on 5 8 in Centers Uninsulated Item 6 AWG 4 AWG T B 54205 Die Code 24 54206 Die Code 29 Burndy YA6CL2TC14 Die Code 7 YA4CL2TC14 Die Code 8 Panduit LCD6 14A L Die Code 24 LCD4 14A L Die Code 29 Table 3 TPA Output Ring Lugs 10 Screw Terminals Nylon Insulated Except Where Note...

Page 17: ...NO NC C PWR ALARM FUSE ALARM BAY ALARMS CONTACTS ACTIVATE NO NO NC C NC NC NO C C A A R R 1 2 3 4 TPA OUTPUT RTN A INPUT A TPA OUTPUT BATT A GMT OUTPUT RTN A GMT OUTPUT BATT A INPUT B PWR A PWR B TPA GMT FUSE ALARM CR MJ MN C GND HOLDER LEDS Panel is not shipped with operable bay alarms 2 1 3 4 5 C GND C GND TPA FUSE GMT OUTPUT BATT B GMT OUTPUT RTN B TPA OUTPUT BATT B TPA OUTPUT RTN B TPA FUSE HO...

Page 18: ... fuses REAR VIEW ROTATED TOP VIEW FRONT VIEW Universal Bracket Reversed for 23 Rack Holes Accommodate EIA WECO Mounting Patterns Pull Out Designation Card Below Replacable Alarm Board 1 72 4 37 1 00 2 54 23 00 58 42 22 31 56 67 19 00 48 26 18 31 46 51 17 25 43 82 11 86 30 14 0 10 0 25 1 00 2 54 2 00 5 08 1 00 2 54 0 39 0 98 10 01 25 42 1 15 2 92 T P A P A T GMT GMT 0 75 1 90 0 46 1 17 0 32 0 81 1 ...

Page 19: ... Telect Inc All Rights Reserved 123518 9 A0 1 509 926 6000 telect com 17 Dual Feed 200A 4 5TPA GMT FuseAlarm Panel Power 009 8005 0404 009 8005 0404G 009 8005 0404L Applies to 009 8005 0404G ...

Page 20: ...ect Inc All Rights Reserved 123518 9 A0 1 509 926 6000 telect com 18 Dual Feed 200A 4 5TPA GMT FuseAlarm Panel Power 009 8005 0404 009 8005 0404G 009 8005 0404L Applies to 009 8005 0404L and 009 1000 1033RE ...

Page 21: ... Panel Power 009 8005 0404 009 8005 0404G 009 8005 0404L Telect assumes no liability from the application or use of these products Neither does Telect convey any license under its patent rights or the patent rights of others This document and the products described herein are subject to change without notice ...

Page 22: ... Telect Inc All Rights Reserved 123518 9 A0 1 509 926 6000 telect com 20 Dual Feed 200A 4 5TPA GMT FuseAlarm Panel Power 009 8005 0404 009 8005 0404G 009 8005 0404L ...

Reviews: