background image

SGC 11 - USER MANUAL 

Space Guard Series

 

 

Photoelectric light curtain controller 

 

 

Website:  www.telcosensors.com

 

 

Warning

 

V 1.1 Part Number: 0666220649

 

E-Mail:     [email protected] 

 

This device is not to be used for Personnel Protection in Machine 

Guarding Safety applications. This device does not include the self-

checking redundant circuitry necessary to allow its use in personnel 

machine guarding stand-alone safety applications. 

April 2019 edition 

 

Made in Denmark

 

Telco A/S reserves the right to make changes without prior notice 

 

 

tel 

EN 

Product Data 

 

Electrical Data 

Supply voltage 

ac 

24 V ac, 115 V ac or 230 V ac 

dc 

24 V dc 

Voltage tolerance 

ac  

-12 % / + 6 % 

dc 

+/- 15 % 

Current consumption 

Max. 15 VA 

Output 

Relay 

1 open / 1 close, 250 V ac  / 3 A, 120 V ac / 5 A 

Transistor NPN 

Max. 24 V dc / 100 mA 

 

Environmental Data 

Temperature, operation 

-10 to + 40 ºC 

Sealing class 

IP 20 

Approvals 

 

 

Available Models 

Model 

Supply Voltage 

Output  

SGC 11 A 

300 

230 V ac 

Relay and NPN 

301 

115 V ac 

302 

24 V ac 

500 

230 V ac 

Relay 

501 

115 V ac 

502 

24 V ac 

Note:  1. Detectors to be ordered separately. 

 

2. All controllers can be used with a 24 V dc supply voltage. 

 

Connection

 

 

Wiring Diagrams

 

 

 

 

 

 

 

 

 

 

 

Relay and NPN output 

 

 

 

 

 

 

 

 

  Relay output 

 

Installations & Adjustments

 

 

Installation

 

Connect the SGR detector to the RX connector input and the SGT detector to the 

TX connector input. 

Connect either AC power supply to the terminals marked 0 and 2, or connect 24 V 

dc power supply to the terminals  and -. DO NOT turn power on. 

Warning:

 DO NOT connect AC and DC power supply at the same time 

Connect terminal    to earth or machine frame. 

 

Connect to relay on terminal NO, COM, NC or to transistor output on terminal SIG 
(signal), 

 

 (ground) according to your application. For “safety” relay operation use 

NO and COM outputs. 

Connect to the Alarm and Time-out outputs on terminals AL, TO and 

 

 according 

to your application. 

Turn the gain potentiometer to max sensitivity (fully clockwise). 

Make sure Operation Mode (SW2 DIP-switch nº 2 : OFF) has been selected. Make 

sure Long Range has been selected (SW2 DIP-switch nº1 : ON). 

Turn power on after double checking your wiring, and checking for correct power 

supply voltage. 

If the controller indicates a broken beam despite a clear optical path between the 

detectors, switch to Diagnostic Mode. Wait approx. 15 sec. The RXERR and 

TXERR LED’s will indicate the faulty detector. Change or clean the faulty detector 

and switch to Operation Mode. 

10 

For operation at ranges below approx. 3 m it is recommended to adjust the 

sensitivity, following the calibration procedure below. 

Turn the potentiometer to minimum (fully anticlockwise), and then turn slowly 

clockwise until the detector see each other. If the adjustment appears too delicate, 

then switch to Short Range and re-adjust. 

11 

In applications with operation at short range it is recommended to use Automatic 

Sensitivity Control Mode, to ensure that the light beams easily can be broken. If 

there is a need for constant excess emitted power at short range, use Fixed 

Sensitivity Mode. 

12 

Select Relay Mode and time-out according to your application. 

 

Output Logic

 

Detection 

Output 

mode

 

Relay 

Transistor 

Output 

Output 

indicator 

(yellow led)

 

Present 

 

 

 

 

 

 

 

 

Dark 

operated 

 

Closed 

On 

Light 

operated 

 

Open 

Off 

Absent 

 

 

 

 

 

 

 

Dark 

operated 

 

Open 

Off 

Light 

operated 

 

Closed 

On 

 

Long/Short Range Selection 

Long range 

Enables the system to operate at 100% (maximum 

range). Range up to 5 m. 

 

 

 

 

Short range 

Enables the system to operate at 60% of maximum 

range. Range up to 3 m. 

 

 

 

 

 

Diagnostic/Operation Mode                                                                                                SW2 

Diagnostic 

mode 

This switch is only for service. When activated, the 

controller initiates a self test. If there is any error in 

transmitter or in the receiver, the TXERR LED or 

RXERR LED are activated. For instance, 

contamination on detectors, bad connections,… 

 

 

 

 

Operation 

mode 

Operating mode. 

 

 

 

 

 

Automatic Sensing/Fixed Sensing                                                                                     SW2 

Automatic 

Sensing 

Control 

Automatic Sensitivity Control Mode is 

recommended in applications with operation at 

short range, to ensure that the light beams easily 

can be broken. 

 

 

 

 

Fixed Sensing 

Allows to adjust manually the sensitivity of the 

system via the potentiometer. 

 

 

 

 

 

Buzzer On/Off                                                                                                                       SW2 

Buzzer On 

Activates the buzzer in parallel with the output. 

 

 

 

 

Buzzed Off 

Deactivates the buzzer. 

 

 

 

 

 

Time-out function                                                                                                                SW1 

After one or more beams (selectable from 0 to 32) have been broken for more than a preset 

period of time (selectable from approx. 15 seconds to 10 minutes) the Controller 

will ignore the broken beams, and thus allow the system to operate with the remaining light 

beams. 

The maximum number of channels time-out can be 

selected from 0 to 32 by using the DIP-switches nº 1,2 and 

3,  on the SW1 switch. Please, refer to Fig. 1 

 

The time-out delay time can be selected from approx. 15 

seconds to 10 minutes by using the DIP-switches nº 5,6 

and 7, on the SW1 switch. Please, refer to Fig. 1 

 

 

 

NC 

 

NO 

 

 

NC 

 

NO 

 

 

NC 

 

NO 

 

 

NC 

 

NO 

 

dc-supply  ac-supply 

AC 

SUPPLY 

24 VDC 

SUPPLY 

Relay output 

dc-supply  ac-supply 

AC 

SUPPLY 

24 VDC 

SUPPLY 

Relay output 