Installing  the Sensor 

!WARNING!

Before performing  service or  maintenance opera­

tions on the systems,  turn OFF main power switch­

es to the unit. Electric shock can cause personal 

injury.  Please read and follow the wiring  instructions 
precisely;  miswiring may cause permanent damage 

to the product. 

Basic Installation 

1. Separate the case into its front and rear sections.

2.  Secure the rear section of the case to the wall or 

junction box using the supplied screws, and make

necessary wire connections.

3.

Select Voltage or Current output option and Voltage

range (0-1 0 V or 0-5 V) using the SW1 as shown on
the internal label (Figure 1) and Table 1.

Note: 

SW1  controls both CO2 and Temperature 
outputs simultaneously. 

Factory default setting is Voltage outputs 0-1 0V. 

Table:  1 

Voltage and Current Output Options 

Switch 

Switch 

Configuration 

#1 

#2 

Down, 

Down, 

Factory default setting 

Low 

Low 

CO2 

0-1 0 V / 0 - 2000 ppm 

Temperature 0-10 V/ 0 - 50 °C 

Up, High 

Up, High 

CO2 

0-5V/ 0 - 2000 ppm 

Temperature 0-5 V/ 0 - 50

°

Down, 

Down, 

CO2 

4-20 

mN 

0 - 2000 ppm 

Low 

Low 

Temperature 4-20 

mN 

0 -

50

°

Up, High 

Up, High 

RESERVED 

4.

Mount the Controller on the base by aligning the top

clips and then securing to the bottom clips.

Secure the  Ventostat with the supplied set screw.

A one-minute stabilization warm up will take place.

Amphenol 

Advanced Sensors 

TELJ1il. 

Telaire T5100-LED  Series CO2 

and Temperature Sensor 

User Instructions 