AFA4000/E
VAV Airflow Controller / p.116
If the sash light beams intermittently sense the glass object, ensure
sw1
is set to Off (short
range) and repeat steps 5 to 14 above.
If the beam is broken when the path is clear and adjusting the Gain Potentiometer does not
resolve this situation, either:
Switch
sw2
On
(Diagnostic mode). After approximately 15 seconds the
RX ERR
and
TX ERR
LEDs (Figure 63) will indicate if there is a faulty beam:
•
RXERR Red LED
On
–
Faulty receiver
•
TXERR Red LED
On
–
Faulty transmitter
Or:
Clean or replace the faulty component and set
sw2
to
Off
(Operation mode).
7.6.8
Tilt switch
No user calibration of the Tilt Switch is possible. When using a Tilt Switch, ensure that the top
panel of the fume hood is closed before switching on the Auto Sash Control Unit.
7.6.9
Sash position sensor
No user calibration of the Sash Position Sensor is possible. The sensor provides sash position
data to the Auto Sash Controller, relative to its starting position.
7.6.10
Personnel sensor
The sensor is self-calibrating and does not need adjusting.
For optimum performance, ensure the detection field in front of the fume hood is clear from
objects and personnel when powering up the Auto Sash Control Unit.
The sensor will be fully operational approximately 10 seconds after the sensor is powered up.
The LED on the sensor will be green if the detection area is clear and red if it is not clear.
To test that the sensor is operational, listen to whether the internal relay clicks when standing in
front of the fume hood and when walking away.
7.6.11
Sash low switch
No user calibration of the Sash Low Switch is possible.
7.6.12
Auto Stop
The Auto stop feature uses the calibrated middle position as the stop position
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...