If the airflow display is unstable following the calibration because of environmental turbulence
or sensor position and cannot be rectified, then it is possible to adjust the sensitivity of the
displayed value using the Display Smoothing parameter in the Cal Config menu. The controller
displays the velocity value as a rolling average over time and is adjustable over 1 to 100 seconds.
Note
The control output is not affected by the display smoothing so will provide fast response
control based on the sensor output. If the control output is unstable due to turbulence on
the sensor, then the output can be tuned to give stable control in the Econ Config menu
(see section 8.2).
7.2
Auto Sash Controller 1, 2 or 3 position.
This section describes the calibration of the Auto Sash Controller from the AFA4000/E/AS.
Note: Refer to section 7.6 to calibrate the Auto Sash Controller from the Auto Sash keypad
1.
From the
Run Screen
press and hold the
Mute
button for 5 seconds until the
Main Menu
is
displayed.
2.
Use the
↑
/
↓
buttons to select
Set Up Auto Sash
. The display shows the message
TEL SASH
CLOSER
.
3.
Press the
Mute
button to display the current Hardware and Software version, for example,
1.
HW2.0 FW1.1
.
4.
Press the
↓
button to scroll down and select
Setup Menu
and press
Mute
.
5.
Enter the password (the factory default password is 1-0-0-1) and press
Mute
to continue.
6.
In the Setup menu the controller displays
System Profile
.
7.
Use the
↓
button to scroll through the menu, select
Sash Settings
and press
Mute
.
8.
In the
Autosash configuration menu
, the display will show
1. Enabled
.
9.
Use the ↓ button to scroll through the menu and select
4. Calibration
and press
Mute
.
10.
Follow the on-screen instructions and set the sash to the centre opening, for example, 250
mm.
11.
Press the
↓
button to find which arrow represents the sash closing and press
Mute
. This step
shows the controller which direction the motor needs to drive to close the sash.
12.
Close the sash and press
Mute
. This step sets the sash position sensor output, 0 V position.
13.
Fully open the sash and press
Mute
. This step sets the sash position sensor output, 10 V
position.
14.
Set the sash to the lower position, for example, close and press
Mute
.
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...