Sales Support Bulletin
-
No. 5
NC375 Radio Paging Voltage Interface
Room Number Programming Instructions
Part Numbers involved: NC375
We are happy to announce the ability to field program architectural room numbers into the NC375
Voltage Interface is now available. The instructions have been added to the installation manual, IL679 but
feel a condensed version reference may help make it easier in the field and is found below.
Theory: The NC375 offers the ability to take an annunciated point from a hard-wired TekTone nurse call
system and process it through the interface and to a transmitter ultimately displaying on a pocket pager.
Using the included programming software, you will be making a data file where architectural information is
entered and saved to disk. This data file will then be sent to the voltage interface where it will be retained
in memory. This will allow changes to be made to the original file later allowing the equipment to reflect
changes in the facility. The “file” may be repeatedly revised and “re-sent” to the NC375 Voltage Interface
as needed.
Required materials:
Computer/Laptop w/ 3½” disk drive
Serial Port available (COM 1, NOTE: The COM port setting may changed in the program under the
devices menu)
Serial Cable supplied with NC366A transmitter (CT365)
Programming Software disk
Procedure:
1.
Install programming software from 3½” diskettes supplied with the NC375, following the computer
prompted directions. Once completed turn computer off.
2.
Connect serial cable from COM 1 port to the port on the NC375 voltage interface.
3.
Verify dipswitch settings on the NC375 per pg. 3.
4.
Power up computer and NC375 unit.
5.
Start the NC375 program (the following will appear).