Astra-MA 

Addressable mark 

 
 

 

User guide 

Manufacturer: 
ZAO NTC TEKO 

420108, Russia, Kazan,  
Gafuri str., 71  
Tel.:+7(843) 528-03-69 

[email protected] 
www.teko.biz

 

 

Made in Russia 

 

  

           

Rev. MA-v1_2_instr_en

  

  
 

 

 

 

1  FUNCTION 

•  Addressable  Mark  Astra-MA  (further 

Astra-MA

)  is 

designed    to  receive  notifications 

via  two  program-

mable

 alarm loops (AL) from non-addressable devices 

with a “dry contact” output and to transmit notifications 
via  Signaling  Line  Circuit  (SLC)  through  Astra-A  RPA 
(RPA)  into  Astra-812  Pro  or  Astra-8945  Pro  (version 
5_0 and above) Control Panels. 

• 

Astra-MA

  does  not  provide  connection  of  detectors 

with loop power supply. 

• 

Astra-MA

 provides programming of AL from the PKM 

Astra Pro. 

• 

Astra-MA

  provides  monitoring  of  the  operability  of  a 

fire-type AL for open and short circuit. 
• Astra-MA is powered from the RPA through the SLC 
power circuit. 
  

 
02  

SPECIFICATIONS

 

Power supply voltage, V ................................  7,0 - 27,6 
Consumption, mA not more

…. .................................. 0,5 

Maximum length SLC interface, m

……………….  1000  

AL Parameters (terZ1-,+Z2-)

Short circuit current, mA, 

not more…………………….1 

AL wire resistance, Oh

m, not more…………………..50 

AL integration time, ms…………………….70/300/500 
AL resistance of different types and states,  
kOh

m………………………………………...see manual 

Dimensions, mm…………………………… …87x54x28 

Operating Conditions 

Temperature range, 

°

С

 ....................... from - 30 to + 55 

Relative air humidity

, % ...................... up to 93 at +40

°

С 

 

without moisture condensation 

3  DELIVERY  SET 

Delivery  set  includes: 

fastening  parts  (dowels  -  2, 

screws - 2), resistor 3.9 kOhm 

– 2. 

 
 
 
 
 

 

4  INDICATION

 

STATUS

 

LED 

Control 

Panel 

Fire / alarm/ 
AL fault 

 

Opening 

 

     + 

Power failure 
(below 7.5V) 

3 times flashes with a 
period of 25 sec. 

 

Testing (via 
ASTRA-942)* 

1 time flash for 2 sec. 

 

Registration 
(via ASTRA-
942)* 

1 time flash for 2 sec. 

 

“*” - service indication used during commissioning 
and Astra-MA maintenance 
“+” - a notification is issued 
“-” – a notification is not issued 

 
5 INSTALLATION  PROCEDURE  
1) 

Push the cover latch out of the groove in the 

base. Remove the cover. (pic. A) 

 

pic. A                           pic. B 

 

2) 

Bend back the hooks on the base. Remove the PCB. 

(pic. B) 

3) 

Make  a  markup  at  the  selected  installation  location 

according to the attached base. (pic. C)  