1  FUNCTION 

•  Isolator  (further  “Isolator”  or  “device”)  is  an 
unaddressed  device  designed for  installation  in 
SLC  or  RS-485  interface  line,  formed  by  the 
Control Panel Astra Pro. 
•  The  Isolator  is  designed  for  automatic  isola-
tion of an SLC segment or a section of the RS-
485  interface  line  (with  extender),  in  which  a 
short  circuit  has  occurred.  The  Isolator  is  de-
signed  to  protect  and  maintain  the  system 
operability in case of a single failure of the SLC 
line, to accelerate the search for the location of 
the failure. 

• The Isolator is powered by: 
- in SLC - the Extender through the SLC power 
circuit, 
-  in  RS-485  interface  -  the  nearest  Extender 
power supply circuit. 
In  case  of  power  failure,  the  recovery  of  the 
Isolator SLC power line occurs when the power 
supply voltage is higher than 15 V. 

 

2  

SPECIFICATION

 

Power supply voltage, V ....................  7.5 

– 27.6 

Current consumption, mA, no more than ......... 4 
Maximum cable cross-section for connecting to 
terminals, mm ...............................................2.5  
Overall dimensions, mm ..................... 

87×54×28 

Operating Conditions 

Temperature range, 

°

С

 ............ from - 30 to + 55 

Relative air humidity

, % .......... up to 93 at +40

°

С 

 

without moisture condensation 

3  DELIVERY  SET 

Dowels 

– 2 pcs., screws – 2 pcs., sticker – 2 pcs. 

 
 
 

4  INDICATION 

Table 1 

Status

 

Reason 

LED 

Standby mode 

Norm 

ON 

Power failure 
L1 or L2 (SLC 
only) 

Short circuit of 
the power 
supply line 
connected to 
L1 or L2, or 
voltage below 
8 V 

1 time flashes 

with a period of 

3 sec. 

Failure of data 
line L1 or L2 

Short circuit of 
the SLC data 
line or RS-485 
interface 
connected to 
L1 or L2 

2 times flashes 

with a period of 

3 sec. 

5  OPERATING MODES CHANGE 

By  directing  a  laser  beam  of  Astra-942  laser 
pointer  to  the  Isolator  indicator  we  can  do  the 
following: 

disable/enable  indication  of  Isolator  in 

StandBy mode (red LP button) 

disconnect/connect  a  part  of  SLC  circuit 

(power and data interface) (bottom LP button) 

disable/enable  the  line  Isolator  function 

(middle LP button). 

 

Note:  

1.The Isolator operating modes switching is performed 
at each laser beam directing to the Isolator indicator. 
When the Isolator is illuminated again  by pressing the 
same button (not earlier than 5 sec. after the previous 
exposure), the operating mode of the Isolator is invert-
ed. 
2.The  Isolator  "memorizes"  its  state  before  the  power 
is turned off and after the power is restored, it restores 
its  functions  in  the  modes  established  before  the 
power was turned off. 

 