1  FUNCTION 

The detector is designed to detect fires accom-
panied by the appearance of smoke, generate a 
fire  notice  and  transmit  notifications  via a  radio 
channel  to  the  Astra-812  Pro  control  panel 
directly  or  through  the  Astra-WE  433  radio  ex-
tender also to the Security Hub controller. 

The  detector  supports two-way  radio exchange 
mode.

 

2  SPECIFICATIONS 

 

Detector`s sensitivity, dB/m

 ....... from 0.05 to 0.2 

Response time, sec., max ..............................10 
Installation height, m, max .............................12

 

Wireless coverage range  
(line-of-sight), m ........................................... 300 
Operating frequency range, MHz ................. 433

 

Power supply voltage, V .............. from 2.1 to 3.0 
Overall dimensions, mm ...................  

Ø106 × 60

 

Operating Conditions 

Temperature range, 

°

С ............from - 30 to + 55  

Relative air humidity, % ........ up to 93 at + 40 

°

С 

                                       

without moisture conden-

sation 

3  DELIVERY  SET

 

Delivery set includes: battery, 3.0 V, (CR123A) 
- 2 pcs.(installed), protective cover (red) 

– 1 

pcs., user guide 

– 1 pcs.

 

 

 
 
 
 
 
 
 

 
4  INDICATION 
 

Notification 

Indication 

Boot time 

1x red flash

 then 1x white 

flash 

Norm 

1x red flash

 in 60 sec. period 

Fire alarm 

1time/2 sec red flash

 until the 

fire factor is eliminated. 

2x  flashing

 in  a  period  of 

25 

sec.

 when eliminating the fire 

factor  before  receiving  a 
command from the controller 

Test 

1time/2 sec red flash 

during 

30  sec.

  when  receiving  the 

test command from the Astra-
942 laser remote control 

Failure 

3x  red  flash

  in 

25  sec.

  peri-

od  

Power failure 

3x  red  flash

  in 

25  sec.

  peri-

od 

Tampering / 
Restore tam-
pering 

1x red

 flash  

Search con-
nection 

5x white flash in 1 sec.

 

 

No connection 

2x white flash in 25 sec. 
period 

Reset 

2

x white flash in 1-2 sec.

 

 

 

Notes 

1 When the message “Power failure” appears, 
the battery must be replaced within two months. 
2 Indication of notifications "Power failure", "No 
network", "Search for network" goes off 60 
minutes after

 

turning on the power supply. The 

indication turns on again for 60 minutes after 
receiving

 

the "Test" command from the Astra-

942 laser tester. 

 