The tekmar Remote Display Module (RDM) 040 provides the user with a remote interface to any tekmar

control that is tekmar Net

TM

 (tN2) capable. The RDM can be used to view and/or adjust the settings on

the control that it is connected to, or on any Room Temperature Unit (RTU) that may be connected to the
control. The RDM can display any of the system and status indicators visible on the control or RTU. It also
has a built in alarm contact that can be used to trigger an external alarm if either a control or sensor
error occurs.

Installation

STEP ONE 

REMOVING THE FRONT COVER 

Place a screwdriver or similar object into the small slot located in the top
of the RDM. Push the screwdriver against the plastic tab, and pull the top
of the front cover so that it pivots around the bottom edge of the RDM.

STEP TWO 

MOUNTING THE RDM 

The base of the RDM should be securely installed in the desired location.
Mount the RDM directly to the desired location using two #6 - 1” screws.
The screws are inserted through the mounting holes and must be
securely fastened to the desired location. If possible, at least one of the
screws should enter a wall stud or similar surface. If the RDM is to be
mounted to a 2” x 4” electrical box, order an Adaptor Plate 007. This plate
mounts to the electrical box and the RDM will then mount to the plate.

STEP THREE 

WIRING THE RDM 

Run 18 AWG twisted pair or similar wire between the RDM and the control. Insert the wires through the hole provided in the back of
the RDM enclosure and connect them to the 

Com and the tekmar Net

TM

 (TN2) terminals. Do not run the wires parallel to telephone or

power lines as this may interfere with the operation of the RDM. If the RDM wires are located in an area with strong sources of
electromagnetic noise, shielded cable should be used or the wires can be run in a grounded metal conduit.

NOTE: Do not apply power to the RDM. The RDM is to be wired directly to the control. The
connection between the control and the RDM is polarity sensitive. The Com terminal of the RDM

must be connected  to the Com terminal of the control and the tekmar Net

TM

 (tN2) terminal of the

RDM must be connected to the  appropriate terminal of the control. If the wires are reversed, the
display on the RDM will remain blank and the control will display a short circuit error for the tekmar

Net

TM

 (tN2) device.

STEP FOUR 

WIRING A REMOTE ALARM 

The RDM comes with a built in alarm contact. This contact will close anytime either a sensor
or control error is detected by the control. The contact will remain closed until the error is
cleared. To clear the error message on the RDM and turn off the alarm relay, refer to the
control Data Brochure. This contact will also close if a Warning in the control is triggered.
However, if a warning is triggered, the alarm contact will only remain closed for 60 seconds.
After 60 seconds, the warning message will continue to be displayed, but the alarm contact
will be shut off. To clear the warning message, the keypad of the RDM must be pressed as
described in the control Data Brochure.

Between terminals 1 and 2, the contact is capable of switching a low voltage signal that is
less than 0.5 Amps. This switch can be used to operate a low voltage alarm device directly,
or it can be used to energize an external relay to trigger a line voltage or high current
alarm device.

STEP FIVE 

INSTALLING THE FRONT COVER 

Align the hinges on the bottom of the front cover with the bottom of the RDM mounting base.
Pivot the front cover around the bottom hinges and push the top against the mounting base
until it snaps firmly in place.

 - Data Brochure

D 040

06/99

Remote Display Module (RDM) 040

24 V(ac)

1

2

3

4

Com

tN2

Warning

Low Voltage

Alarm

24 V(ac or dc)

To control

#6 - 1” screws

Install

ing the

front c

over

Item

Menu

View

1 2

%
1

°

F

DHW

Occ

1

2

3

4

Com

tN2

Warning