FIRE ALARM DETECTOR

TECHNICAL SPECIFICATIONS

INSTALLATION

INSTALLING THE BASE

To ensure proper fit of the detector head to the base, all wires should be properly dressed at installation by positioning all wires flat 
against terminals and fastening the wires away from connector terminals. The detector base can be mounted directly onto most standard 
electrical junction boxes.

INSTALLING THE HEAD

Align detector components using provided alignment marks on both the head and base. Align detector mark and short alignment mark on 
base. Fit the detector head onto the base and twist clockwise to secure it. After all detectors are installed, apply power to the control unit . 
Test the detectors as described below.

TESTING

All remote signalling systems, releasing devices and extinguishing systems should be disconnected during the test period and 
reconnected at the conclusion of testing. After powering the detector, check to see the indicator LED flashing every 5 seconds. If the LED 
fails to flash, it indicates the non-functioning of the detector or fault wiring. Re-check the wiring or replace the detector if necessary. 

SMOKE: Allow smoke from a cotton wick or test smoke aerosol to enter the detector’s smoke chamber for at least 10 seconds. When 
sufficient smoke has entered, the detector will signal an alarm. This will be indicated by the illumination of the 2 Red LEDs provided. Make 
sure to clear smoke out of the chamber before resetting in order to keep the detector at its current sensitivity setting.

HEAT: The detector to be tested should be subject to a flow of warm air at a temperature of between 65°C and 80°C. This requirement can 
be met by some domestic hair dryers. Switch on the warm airflow and check that the temperature is correct and stable. From a distance of 
several cms, direct the airflow at the guard protecting the thermistor. The detector should alarm within 60 seconds. Upon alarm 
immediately remove the heat source and check that the Red LEDs of the detector are illuminated. If a detector fails to activate within 60 
seconds, confirm connections and programming. If necessary replace unit. Note: After testing, check that the system is returned to 
normal operation. Notify the appropriate authorities that the testing procedure has been completed and the system is active again.

MAINTENANCE

The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a 
low power vacuum cleaner.  

   

>> DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR

Detector Head

Detector Base

Alignment Marks

ZEOS-C

ma_zeosc_01_010001_en_180716

MADE IN PORTUGAL - EU

10 V to 30 V DC

Heat: 7 uA / Smoke: 33 uA / Smoke & Heat: 35 uA

24 mA - Alarm LEDs

According to EN54-5 or/and EN54-7

0.5-2.5 mm²

20 seconds max.

White / ABS

95% RH Non-Condensing

0°C to 50°C / -10°C to 85°C

100 mm (D) x 50 mm (H) inc. base / 144 g inc. base

ORION, ORION MINI, ORION EX, ORION-PLUS, QUAD ZMU and ZMU

SUPPLY VOLTAGE

CURRENT - QUIESCENT

CURRENT - DEVICE IN ALARM

SENSITIVITY

CABLE SIZE

RESET/START-UP TIMES

COLOUR / CASE MATERIAL

MAX. HUMIDITY

NORMAL / TRANSIENT OPER. TEMPERATURE

DIMENSIONS / WEIGHT

COMPATIBILITY

ORDER CODE

DESCRIPTION

ZEOS-C-S
ZEOS-C-H
ZEOS-C-SH

|  CERTIFICATE  |

PHOTOELECTRIC SMOKE DETECTOR

RATE OF RISE/FIXED TEMP HEAT  DETECTOR

MULTISENSOR  SMOKE & HEAT DETECTOR

1328-CPR-0705

1328-CPR-0706

1328-CPR-0704

MECHANICAL SPECIFICATION