Installation and maintenance manual
INFINEE chillers
TECUMSEH EUROPE S&L
2 av. Blaise Pascal, 38090 Vaulx Milieu
Tel.: +33 (0)4 74 82 24 00 - www.tecumseh.com
ENGLISH
32
Version: 2020-01
Performances : ambient temperature 35°C
Maximum power 85 Hz
Ambient temperature
35°C
Temp. Water
Input/output
Glycol
Power
in cold
Power ABS
Without pump
Power ABS.
Total
Water flow
-4°C /-8 °C
35%
20.5 kW
10.2 kW
11.3 kW
5.1 m
3
/h
1°C /-3°C
35%
24.2 kW
11.6 kW
12.7 kW
6.2 m
3
/h
7°C / 3°C
35%
28.9 kW
13.6 kW
14.7 kW
7.4 m
3
/h
11°C / 7°C
35%
32.1 kW
15.3 kW
16.3 kW
9.3 m
3
/h
19°C / 15°C
35%
38.5 kW
19.6 kW
20.7 kW
11.2 m
3
/h
Partial load 70 Hz
Ambient temperature
35°C
Temp. Water
Input/output
Glycol
Power
in cold
Power ABS
Without pump
Power ABS.
Total
Water flow
-4°C /-8 °C
35%
17.7 kW
8.2 kW
9.2 kW
4.4 m
3
/h
1°C /-3°C
35%
21.0 kW
9.2 kW
10.3 kW
5.4 m
3
/h
7°C / 3°C
35%
25.3 kW
10.6 kW
11.7 kW
6.5 m
3
/h
11°C / 7°C
35%
28.4 kW
11.8 kW
12.8 kW
8.2 m
3
/h
19°C / 15°C
35%
34.6 kW
14.6 kW
15.6 kW
10.0 m
3
/h
Partial load 50 Hz
Ambient temperature
35°C
Temp. Water
Input/output
Glycol
Power
in cold
Power ABS
Without pump
Power ABS.
Total
Water flow
-4°C /-8 °C
35%
13.5 kW
5.6 kW
6.7 kW
3.4 m
3
/h
1°C /-3°C
35%
16.1 kW
6.3 kW
7.3 kW
4.1 m
3
/h
7°C / 3°C
35%
19.7 kW
7.1 kW
8.1 kW
5.1 m
3
/h
11°C / 7°C
35%
22.2 kW
7.7 kW
8.8 kW
6.5 m
3
/h
19°C / 15°C
35%
27.7 kW
9.1 kW
10.2 kW
8.0 m
3
/h
Partial load 25 Hz
Ambient temperature
35°C
Temp. Water
Input/output
Glycol
Power
in cold
Power ABS
Without pump
Power ABS.
Total
Water flow
-4°C /-8 °C
35%
9.9 kW
3.9 kW
4.9 kW
2.5 m
3
/h
1°C /-3°C
35%
12.0 kW
4.3 kW
5.3 kW
3.1 m
3
/h
7°C / 3°C
35%
14.7 kW
4.8 kW
5.8 kW
3.8 m
3
/h
11°C / 7°C
35%
16.8 kW
5.1 kW
6.2 kW
4.9 m
3
/h
19°C / 15°C
35%
21.2 kW
5.9 kW
6.9 kW
6.2 m
3
/h