V6.x // 06-2016 

Setup and Operation 

P. 1

 

 

Start-up  +  Operation

  

 

  

Electronic pneumatic tank measurement system 

of the

 

e-litro

®

 series

 

 

 

 

e-litro

   

 

      

SW-Version  V6.0x

 

 

 

 

e-litro secu4

   

 

      

SW-Version  V6.0x

 

 

 

 

e-litro net

   

 

 

      

SW-Version  V6.0x

 

 

 

 

e-litro gsm 

  

   

      

SW-Version  V6.0x 

    

  

 

 

for tank sizes up to max. 10,000 liters 

                                            CONTENT: 

Installation and mounting 

  

4

 

Control elements and display 

  

ALARM and QUIT-button for secu4 

  

Device setup and programming 

  

7

 

Programming examples 

  

10

 

Tank with interior mantle 

  

11

 

Special settings 

  

12

 

Error messages / Error indication 

  

14

 

 - for device type  e-litro net 

  

15

 

 - for device type  e-litro gsm 

  

17

 

Electrical connections 

  

18

 

Regualtions and maintenance 

  

20

 

 

 

Summary of Contents for e-litro

Page 1: ...sm SW Version V6 0x for tank sizes up to max 10 000 liters CONTENT Installation and mounting 4 Control elements and display 4 ALARM and QUIT button for secu4 6 Device setup and programming 7 Programmi...

Page 2: ...e applicable for liquid level measurements of tanks operated unpressurized Maximum display value 10 000 liters per tank in case of secu4 The liquid level is indicated by the LCD display The instrument...

Page 3: ...t the secu4 will sound the ALARM and an output relay will interrupt the current loop of the tanker The displaying device and the sensorbox both contain of an alarm sound Such an alarm can be switched...

Page 4: ...skip to next menu step Language Select the operation language German English French in menu step 18 Select displaying mode for e litro and e litro net gsm After setting menu items 1 to 5b the favored...

Page 5: ...assword The device settings can be protected by activating a password under menu item 8 A forgotten password can be requested by contacting TECSON Resetting the secu4 will cause the device to demote i...

Page 6: ...evel action Status Red LED Quit button Beeper loud Relay break contact Display all levels below limit OK off off closed OK level 93 at refill or reserve warning flashes double beeping closed STOP Quit...

Page 7: ...up the measuring range of the level sensor The LITRO Sensor is preset to 250mbar Measuring range max oil tank height water column 250 mbar 3 00 m 2 50 m If a different level sensor to the LITRO Sensor...

Page 8: ...ank shape With excava tion Plastic tank with large cavity Excavation in the middle of the tank s body No ring bandages Cyl 50m 3 Not applicable with e litro displaying devices Bearing chart Value inpu...

Page 9: ...g limit 95 190cm change of value with If e g a water tank may be filled to capacity the filling limit is to be set to a value of 99 all all 6 Display resp for secu4 without function The upper display...

Page 10: ...for secu4 loss of password Menu item 9 24 see ff Steps 9 24 contain special settings which usually will not be needed all After entering setup of step 1 to 7 the standard programming is completed By...

Page 11: ...Example 3 e litro secu4 device with 4 battery tanks 4 x 1250 liters steel tanks with hemicycles at top and bottom 155cm tank height display Fillspace Level for each single tank disable tank filling a...

Page 12: ...displaying Default values Resets all values back to standard 0 For secu4 Exit all do not execute with e litro 10 Trim height Input option for the reference height for calibration of probe and measurem...

Page 13: ...the registered tank numbers Return only for e litro gsm e litro net 17 Input Output Alarm In Choose the function of the alarm contact input Deactive Defines the alarm input to be not operating Opening...

Page 14: ...Relay 1 Off On Enter Not for e litro 24 Reset Resetting the device software ESC Leaves this sub menu without execution Restart New initialization of the device software but parameter setup is left un...

Page 15: ...Please blow through or replace the measurement line preferably with the blue bubbling through pipe of the e litro set As a TEST the bubbling through pipe can be disconnected from the LITRO Sensor E8 s...

Page 16: ...estination In case of entering an individual dest IP no Error N2 message will be shown Important The destination address must be a fixed IP address Otherwise the device retries sending again and again...

Page 17: ...on the prepaid account Error M 5 No mobile network available for the SIM card an external antenna could help Destination number set correctly please check Error M 6 Network or other failure during se...

Page 18: ...us 2 green signal 3 brown minus Bottom right clamping block Power supply 230V AC N L Clamp contact number 1 LITRO sensor input red or white or blue 2 LITRO sensor input brown or black 3 4 Input for a...

Page 19: ...number 1 LITRO Sensor input red white blue 2 ditto black brown 3 data input for additional e litro device 4 ditto 5 alarming contact input 6 ditto 7 8 relay output opening contact normal status is clo...

Page 20: ...er maintenance This needs to be induced by the operator If the secu4 s tanker switch off function is used the password needs to be activated in menu item 8 The password is predefined Maintenance Manuf...