MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________
________________________________________________________________
TECO – Westinghouse Motor Company
9
Step 8
– Select PID control (Sn-64), and Feedback input (Sn – 24) [4 – 20 mA
or 0 – 10 Vdc]
•
Before selecting the parameter(s),
ensure the inverter is in the STOP mode.
•
To activate PID control parameter
(Sn-64)
must be set to
=1
.
•
The Feedback Input parameter
(Sn –24)
is set to
= 1 (AIN, 4-20 mA),
as factory default.
To
select (
VIN, 0-10 Vdc
),
(Sn-24)
must be set to
0.
(See Figs. 3a, 3b and 3c for feedback
connections)
•
To set the parameter(s), follow the navigation procedure as shown next.
key twice
Flashing
1 - Press the
2 - Press the
3 - Press the
key until display shows
4 - Press the
key
(Turn on PID control)
key
0
key to
.
5 - Press the
key
6 - Press the
2 Seconds
7 - Press the
key to return to the main display.
Flashing
1
Flashing
1